 BUILDING REVIEW COMMENTS
 -------- ------ --------
  
  
  
 1)
 EXPLAIN NEW INFORMATION FOR EXISTING
 ROOF TO BE RE-SHEATHED AND NEW OPENINGS
 INCLUDED WITH NO SUPPORTING DETAILS,
 WILL THERE BE A ROOF COVER APPLIED AND
 IF SO A SEPERATE ROOF PERMIT WILL BE
 REQUIRED.
  
 2)
 WHERE IS SECTION 'C' ON SHEET S-1.
  
 3)
 CONCRETE PAD PLACEMENT SHALL BE GIVEN
 SPECIFIC LOCATION NOT GENERAL.
  
 4)
 NATURAL AIR INTAKE CALCULATIONS MAYBE
 REQUIRED NOW THAT THE PLAN CALLS FOR A
 SOLID ROOF, IT WAS ORIGINALLY DESCRIBED
 AS AN OPEN AIR STRUCTURE.
  
 5)
 PRODUCE 2 COMPLETE SETS OF CONSTUCTION
 DRAWINGS FOR PERMIT ISSUE.
  
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710