| Date |
Text |
| 2006-02-08 00:00:00 | ********** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE DISRIBE PROJECT AS BEING |
| | INDICATED ON PLANS ON PERMIT |
| | APPLICATION. IF 2 GENERATORS ETC. |
| | |
| | 2)NOTE: PLEASE SUBMIT MANUFACTURES |
| | SPEC/CUT SHEETS FOR ALL NEW EQUIPMENT |
| | BEING INSTALLED. GENERATOR, |
| | SYNCHRONIZATION EQUIPMENT, FUEL TANKS, |
| | ANY ATS EQUIPMENT ETC. |
| | PLEASE BE SURE ALL LISTINGS AS INDICATE |
| | FROM A NRTL. |
| | |
| | 3)NOTE: PLEASE SEE THE PROPOSED |
| | GENERATORS ARE SUBSTANTIALLY LARGER THAN |
| | THE PREVIOUS ORIGIANL GENERATORS. PLEASE |
| | SEE PLANS SHOW THESE BEING LOCATED HALF |
| | IN AND HALF OUT OF GEN BLDG?? |
| | IF THESE GEN'S ARE GOING TO BE "OUTSIDE" |
| | RAINTIGHT GEN'S, PLEASE BE SURE ALL MIN |
| | CLEARENCE REQUIREMENTS FOR PROPER |
| | VENTILATION IS PROVIDED. PLEASE SEE |
| | FOLLOWING COMMENT. |
| | |
| | 4)NOTE: PLEASE SEE CLEARENCES FOR NEC |
| | CODE COMPLIANCE IS NOT MET PER TABLES |
| | 110.34A. |
| | PLEASE ALSO SEE ENTRANCE, EGRESS |
| | ACCESSED IS ALSO NOT MET PER 110.33A1 |
| | ETC. |
| | |
| | 5)NOTE: PLEASE SEE NO INFORMATION IS |
| | PROVIDED FOR OCP AT GEN'S TO FEED NEW |
| | EQUIPMENT. |
| | PLEASE SEE 445.13 FOR SIZING ETC IFNO |
| | OCP IS PROVIDED AT GEN. ETC |
| | |
| | 6)NOTE: PLEASE PROVIDE MORE INFORMATION |
| | ON TYOE OF CONDUCTORS ARE BEING |
| | INSTALLED FOR 5KV CONDUCTORS. PLEASE SEE |
| | TABLES 310.60 |
| | PLEASE SEE THE # OF CONDUCTORS IN |
| | CONDUITS, AND SIZE , OCP AND AMBIENT |
| | TEMPS, AND VOLTAGE DROP MUST BE |
| | CONSIDERED. UNABLE TO DO THIS AT THIS |
| | TIME. |
| | ** PLEASE COMPLETE. |
| | |
| | 7)NOTE: PLEASE CLARIFY IF THERE IS NEW |
| | OR EXISTING TRANSFER EQUIPMENT. |
| | PLEASE SEE THIS UNCLEAR ON ONE-LINE. |
| | 215.5 |
| | |
| | 8)NOTE; PLEASE PROVIDE THE MIN LOADS FOR |
| | THE EXISTING LOADS WHICH WILL BE LOADED |
| | ON NEW GENERATORS. |
| | IT IS KNOWN THAT THESE WILL BE FEEDING |
| | EXISTING PUMPS ETC, HOWEVER THERE IS NO |
| | RECORD OF THE IMPOSED LOADS. |
| | PLEASE KNOW, THIS OFFICE HAD REVIEWED |
| | DOCUMENTATION IN WHICH THE GEN'S WERE |
| | GOING TO BE 3500KW. |
| | PLEASE VERIFY AND SHOW LOADS. |
| | 215.5 |
| | |
| | 9)NOTE:PLEASE PROVIDE THE LOCATIONS OF |
| | OTHER EQUIPMENT. GEN SW GEAR BUS ETC. |
| | |
| | 10)NOTE: PLEASE SEE THE GC IS APPLYING |
| | ONLY FOR THE INSTALLATION OF THE |
| | GENERATOR. PLEASE KNOW, A PERMIT MUST BE |
| | APPLIED FOR THE ELECTRICAL HOOK-UP AND |
| | INSTALLATION. THIS WILL BE A GEN- ELEC |
| | TYPE PERMIT. PLEASE ALSO KNOW A FUEL |
| | PERMIT WILL BE REQUIRED FOR SCOPE OF |
| | WORK FOR FUEL TANKS, PIPING ETC. |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |