| Plan Review Notes For Permit 06020372 |
| Permit Number |
06020372 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-10 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PERMIT: | | | | | | 1. INDICATE ON THE DRAWING ALL CUT | | | SECTIONS OF PIPE AND CORRESPONDING | | | LENGTHS PER FBC-2004 FUEL GAS CODE. THE | | | ONLY PIPE INDICATED ON DRAWING IS 45' OF | | | 3/4" PE. DROPS AND RISERS LENGTHS AND | | | TYPE OF MATERIAL BEING USED NEED TO BE | | | INDICATED ON DRAWING. ALSO VALVES NEED | | | TO BE INDICATED ON DRAWING, THERE NEEDS | | | TO BE A SHUT OFF VALVE TO GENERATOR. | | | 2. NEED SPECS ON GENERATOR, ORIGINAL | | | GEN-RES PERMIT APPLICATION DENIED AND | | | P/U. THEY NEED TO BE RESUBMITTED AND | | | PASSED BY ZONING BEFORE GAS PERMIT CAN | | | BE ISSUED. | | | 3. LONGEST LENGTH: DRAWING INDICATES | | | 45'. IS THIS THE LONGEST LENGTH ON | | | SYSTEM? | | | 4. TYPE OF GAS, (LP OR NATURAL) | | | INDICATE ON DRAWING | | | 5. TOTAL BTU LOAD ON SYSTEM NEEDS TO BE | | | INDICATED ON DRAWING | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-5621 |
|