| 2006-03-07 00:00:00 | ************ UNSAT ************* |
| | |
| | 1)NOTE: PLEASE BE SURE PLANS REFERENCE |
| | ALL CURRENT CODES AS FOLLOWS. |
| | 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002 |
| | NFPA-72. |
| | PLANS INDICATE THE 2004 FLORIDA |
| | ELECTRICAL CODE? |
| | |
| | 2)NOTE: PLEASE SEE "A" SHEETS WHICH |
| | CONTAIN A RAISED SEALED OVER |
| | "PHOTO-COPIED" SIGNATURE OF ARCHITECT. |
| | PLEASE SEE FLORIDA STATUES, 481.221 |
| | WHICH REQUIRES THE SIGNATURE TO BE |
| | "ORIGINAL"/"WET" SIGNATURE. |
| | THIS IS REQUIRED FOR ALL TRADES WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE SEE MISSING LICENSING |
| | INFORMATION REQUIRED ON TITLE BLOCK FOR |
| | ARCHITECT'S FIRM. FLORIDA ADMINISTRATIVE |
| | CODE61G1-16.004, FLORIDA STATUES |
| | 481.219. |
| | PLEASE ALSO SEE MISSING THE PRINTED AR # |
| | THIS IS REQUIRED FOR ALL TRADES AND ON |
| | ALL SHEETS CONTAINING THE TITLE BLOCK |
| | FOR SAID ARCHITECTURAL FIRM/ ARCHITECT, |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 4)NOTE:PLEASE SEE ENGINEER'S TITLE |
| | BLOCK AS THIS IS MISSING THE "PRINTED |
| | LICENSE" NUMBER AS REQUIED PER FAC |
| | 61G15-23.002. |
| | PLEASE SEE SEE FS 471.025 WHICH REQUIRES |
| | THE LEGAL SIGNATURE FOR ENGINEER. PLEASE |
| | SEE PLANS APPEAR TO HAVE "INITIALS"?? IF |
| | INDEED THIS IS THE "LEGAL SIGNATURE", |
| | PLEASE PROVIDE A SIGNED, DATED AND |
| | SEALED NOTORIZED LTR ATTESTING TO THE |
| | LEGAL SIGNATURE AS SHOWN. |
| | PLEASE KNOW THIS WILL BE PLACED IN OUR |
| | SIGNATURE FILE FOR ANY FUTURE REFERENCE |
| | AS NEEDED. |
| | |
| | 5)NOTE: PLEASE OBTAIN THE CORRECT |
| | "SUITE" INFORMATION AS PERMIT |
| | APPLICATION MENTIONS "C-9" AND THIS IS |
| | NOT AN ACCURATE SUITE #. |
| | PLEASE ADJUST ALL TITLE BLOCKS ON PLANS |
| | ONCE SUITE NUMBER IS KNOWN. |
| | FAC 61G15-23.002, FAC 61G1-16.004 |
| | |
| | 6)NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1 &.2 FOR LIGHTING |
| | CONTROLS, SCHEDULING, ETC. |
| | PLEASE PROVIDE ALL INFORMATION AS |
| | SETFORTH FOR ENERGY CONSERVATION AS |
| | REQUIRED. |
| | PLEASE PROVIDE CALCULATIONS AS NEEDED. |
| | |
| | 7)NOTE: PLEASE SHOW/VERIFY NEW OR |
| | EXISTING "SHOW WINDOW" RECEPTS AS |
| | REQUIRED PER 210.62. PLEAS ADJUST LOAD |
| | CALCUALTIONS PER 220.12A |
| | |
| | 8)NOTE: PLEASE INDICATE THE TRACK |
| | LIGHTING LOADS PER 220.12B |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. THIS WILL TAKE |
| | PLACE ONCE ALL REVIEWS ARE DONE AND |
| | PLANS ARE PICKED UP BEFORE RSUBMITTING. |
| | PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED |
| | REMOVED SHEETS. |
| | |
| | ** PLEASE KNOW, A RESPONSE LETTER FROM |
| | THE DESIGN PROFESSIONALS IN RESPONSE TO |
| | COMMENTS WILL HELP IN EXPEDITING THE |
| | REVIEW PROCESS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |