Plan Review Notes
Plan Review Notes For Permit 06020333
Permit Number 06020333
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-07 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE BE SURE PLANS REFERENCE
 ALL CURRENT CODES AS FOLLOWS.
 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002
 NFPA-72.
 PLANS INDICATE THE 2004 FLORIDA
 ELECTRICAL CODE?
  
 2)NOTE: PLEASE SEE "A" SHEETS WHICH
 CONTAIN A RAISED SEALED OVER
 "PHOTO-COPIED" SIGNATURE OF ARCHITECT.
 PLEASE SEE FLORIDA STATUES, 481.221
 WHICH REQUIRES THE SIGNATURE TO BE
 "ORIGINAL"/"WET" SIGNATURE.
 THIS IS REQUIRED FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 3)NOTE: PLEASE SEE MISSING LICENSING
 INFORMATION REQUIRED ON TITLE BLOCK FOR
 ARCHITECT'S FIRM. FLORIDA ADMINISTRATIVE
 CODE61G1-16.004, FLORIDA STATUES
 481.219.
 PLEASE ALSO SEE MISSING THE PRINTED AR #
 THIS IS REQUIRED FOR ALL TRADES AND ON
 ALL SHEETS CONTAINING THE TITLE BLOCK
 FOR SAID ARCHITECTURAL FIRM/ ARCHITECT,
 WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 4)NOTE:PLEASE SEE ENGINEER'S TITLE
 BLOCK AS THIS IS MISSING THE "PRINTED
 LICENSE" NUMBER AS REQUIED PER FAC
 61G15-23.002.
 PLEASE SEE SEE FS 471.025 WHICH REQUIRES
 THE LEGAL SIGNATURE FOR ENGINEER. PLEASE
 SEE PLANS APPEAR TO HAVE "INITIALS"?? IF
 INDEED THIS IS THE "LEGAL SIGNATURE",
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED NOTORIZED LTR ATTESTING TO THE
 LEGAL SIGNATURE AS SHOWN.
 PLEASE KNOW THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCE
 AS NEEDED.
  
 5)NOTE: PLEASE OBTAIN THE CORRECT
 "SUITE" INFORMATION AS PERMIT
 APPLICATION MENTIONS "C-9" AND THIS IS
 NOT AN ACCURATE SUITE #.
 PLEASE ADJUST ALL TITLE BLOCKS ON PLANS
 ONCE SUITE NUMBER IS KNOWN.
 FAC 61G15-23.002, FAC 61G1-16.004
  
 6)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 &.2 FOR LIGHTING
 CONTROLS, SCHEDULING, ETC.
 PLEASE PROVIDE ALL INFORMATION AS
 SETFORTH FOR ENERGY CONSERVATION AS
 REQUIRED.
 PLEASE PROVIDE CALCULATIONS AS NEEDED.
  
 7)NOTE: PLEASE SHOW/VERIFY NEW OR
 EXISTING "SHOW WINDOW" RECEPTS AS
 REQUIRED PER 210.62. PLEAS ADJUST LOAD
 CALCUALTIONS PER 220.12A
  
 8)NOTE: PLEASE INDICATE THE TRACK
 LIGHTING LOADS PER 220.12B
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. THIS WILL TAKE
 PLACE ONCE ALL REVIEWS ARE DONE AND
 PLANS ARE PICKED UP BEFORE RSUBMITTING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 REMOVED SHEETS.
  
 ** PLEASE KNOW, A RESPONSE LETTER FROM
 THE DESIGN PROFESSIONALS IN RESPONSE TO
 COMMENTS WILL HELP IN EXPEDITING THE
 REVIEW PROCESS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]