Plan Review Notes
Plan Review Notes For Permit 06020332
Permit Number 06020332
Review Stop P
Sequence Number 1
Notes
Date Text
2006-02-22 00:00:00DENIED;
 1)DRINKING FOUNTAIN REQUIRED. SEE
 FBC-2004 PLUMBING TABLE 403.1 (A-2) AND
 410.1.
 2)SANITARY DRAIN FROM BAR AREA AND
 MEZZANINE MUST GO TO SANITARY NOT TO
 GREASE TANK. GREASE TANK SHALL BE CAPED
 OF AT BOTH END, PUMPED AND SANITIZED.
 3)5' TURNING RADIUS DOES NOT EXIST IN
 MENS HANDICAP BATHROOM SHOW WHERE THE
 20% RULE WILL BE USED. ONE URINAL MUST
 BE HANDICAP. SHOW DETAIL ON PLANS, PER.
 FBC-2004 CHAPTER 11 SEC. 11-4.18.1 THRU
 11-4.18.4.
 4)ICE MACHINE DETAIL PAGE P-4 SEPARATE
 DRAIN LINES ARE REQUIRED FOR CUBER AND
 ICE BIN.
 5)EQUIPMENT SCHEDULE MISSING. ( NEEDED
 TO COMPLETE PLUMBING PLAN REVIEW.
 6)ONE SET OF PLANS NOT SEALED.
 7)IF COOKING COOKING EQUIPMENT WAS GAS
 ALL GAS PIPING MUST BE REMOVED BY A GAS
 CONTRACTOR, DEMO PERMIT REQUIRED. ADD
 NOTE ON DEMO PLAN.
 8)PLUMBING FIXTURES, FLOOR DRAINS, AND
 FLOOR SINKS IN KITCHEN AREA MUST BE
 REMOVED SO NO DEAD ENDS EXIST. (NOT
 SHOWN ON DRAWINGS) SHOW ALL DEMO WORK.
 9)PLANS TO BE REVIEWED AND APPROVED BY
 THE HEALTH DEPARTMENT BEFORE RESUB TO
 WPB. CONTACT NAN MC DERMIT
 901 EVERNIA ST
 WPB
 355-3018
 10.WATER RISER. REMOVE AIR CHAMBER
 SYMBALS. LOWER THE WATER HAMMER
 ARRESTORS DOWN. ARRESTORS ARE TO BE
 INSTALLEDCLOSE TO FIXTURES PER
 MANUFACTORS INSTALLATION INSTRUCTIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved