| Plan Review Notes For Permit 06020332 |
| Permit Number |
06020332 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-15 00:00:00 | 1. DEMOLITION, CONSTRUCTION, AND | | | RENOVATION TO COMPLY WITH NFPA 241. | | | | | | 2. EXITS ARE TO REMAIN CLEAR. | | | | | | 3. DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 4. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM ADDITION. | | | | | | 5. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR HOOD, DUCT, AND SUPPRESSION SYSTEM. | | | | | | 6. ON PAGE AO PLANS INDICATE SPACE IS | | | NOT FIRE SPRINKLER PROTECTED BUT ON PAGE | | | A2.0 IT INDICATES THAT FIRE SPRINKLERS | | | EXIST. PLEASE ADVISE. | | | | | | 7. PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 8. ANY STORAGE OR ELECTRIC PLANNED FOR | | | UNDERNEATH OF ELEVATED PLATFORM. | | | | | | 9. BUILDING ADDRESS REQUIRED. A MINIMUM | | | OF AT LEAST 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 10. PANIC HARDWARE REQUIRED ON ALL EXIT | | | DOORS SUBJECT TO AN OCCUPANCY OF 100 OR | | | MORE PERSONS. |
|