Plan Review Notes
Plan Review Notes For Permit 06020332
Permit Number 06020332
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-22 00:00:00********UNSAT *********
  
 1)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FS
 471.025 WHICH REQUIRES THE PLANS TO BE
 SIGNED , DATED AND SEALED BY THE
 ENGINEER OF RECORD. PLEASE ALSO SEE FS
 481.221 FOR ARCHITECT'S.
 PLEASE SEE ONE SET OF PLANS ARE
 PHOTO-COPIES OF SIGNED, AND SEALED
 PLANS.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE BE SURE PLANS REFERENCE
 AND INDICATE THE CURRENT CODES AS
 FOLLOWS ON ELECTRICAL, ARCHITECTURAL AND
 FIRE SHEETS.
 2003 NFPA-101,2002 NFPA-72, NFPA-70 2002
 PLEASE ALSO VERIFY WITH OTHER NOTES
 PERTIAING TO KITCHEN AND ANY POSSIBE
 HOODS PER NFPA-96 2001.
  
 3)NOTE: PLEASE SEE SCOPE OF WORK
 INDICATED ON PERMIT APPLICATION DOES NOT
 CORRELATE WITH THE SUBMITTED PLANS.
 PLEASE SEE PLANS INDICATE KITCHEN WORK
 ETC, YET APPLICATION MENTIONS BAR ONLY??
 SEE COMMENTS FROM OTHER TRADES, AS PLANS
 ALSO INDICATE REMOVAL OF KITCHEN
 EQUIPMENT??
  
 4)NOTE: PLEASE SEE NOT ON PLANS MENTIONS
 ALL RECEPTS WITH IN"6" INCHES (") OF
 SINKS SHALL BE GFI?
 PLEASE SEE 2002 NEC 210.8B3 ETC FOR
 RECEPTS WITH IN 6' (FEET) AND ALL
 15A/20A 125V RECEPTS WITHIN A KITCHEN
 SHALL BE GFI/GFI PROTECTED.
  
 5)NOTE: PLEASE VERIFY LIGHTING CONTACTOR
 BEING REMOVED AND REQUIREMENTS OF FBC
 CHAPTER 13, 13-415.1.ABC.1.1, IT DOES
 NOT SEEM IT IS PERMITTED TO REMOVE THE
 AUTOMATIC MEANS OF LIGHTING SHUT OFF
 UNLESS MEETING THE REQUIREMENTS AND
 PROVIDING NEW MEANS.??
  
 6)NOTE: PLEASE CLARIFY NEW OR EXSITING
 WINDOW RECEPTS ABOVE WINDOWS, 210.62,
 220.12.
  
 7)NOTE: PLEASE CLARIFY/SHOW NEW OR
 EXISTING SIGN CIRCUIT. 600.5
  
 8)NOTE: PLEASE SHOW ALL CONTINUOUS AND
 LARGEST MOTOR LOADS AT 125%.
 215.3,230.42 ETC.
 PLEASE SHOW LOAD CALCULATIONS PER NEC.
  
 9)NOTE: PLEAS VERIFY OCP FOR FACP IS
 SHOWN AS 2POLE 20?
 215.5
  
 10)NOTE: COULD NOT LOCATE A FIXTURE
 SCHEDULE TO CORRELATE WITH THE FIXTURES
 AS NOTED ON PLANS?
 PLEASE SUBMIT.
  
 ** PLEASE SEE OTHER COMMENTS FROM OTHER
 TRADES WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ANY
 OLD/VOIDED SHEETS FROM SETS OF PLANS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  