Text |
| 2006-02-22 00:00:00 | ********UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 AND FS |
| | 471.025 WHICH REQUIRES THE PLANS TO BE |
| | SIGNED , DATED AND SEALED BY THE |
| | ENGINEER OF RECORD. PLEASE ALSO SEE FS |
| | 481.221 FOR ARCHITECT'S. |
| | PLEASE SEE ONE SET OF PLANS ARE |
| | PHOTO-COPIES OF SIGNED, AND SEALED |
| | PLANS. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE BE SURE PLANS REFERENCE |
| | AND INDICATE THE CURRENT CODES AS |
| | FOLLOWS ON ELECTRICAL, ARCHITECTURAL AND |
| | FIRE SHEETS. |
| | 2003 NFPA-101,2002 NFPA-72, NFPA-70 2002 |
| | PLEASE ALSO VERIFY WITH OTHER NOTES |
| | PERTIAING TO KITCHEN AND ANY POSSIBE |
| | HOODS PER NFPA-96 2001. |
| | |
| | 3)NOTE: PLEASE SEE SCOPE OF WORK |
| | INDICATED ON PERMIT APPLICATION DOES NOT |
| | CORRELATE WITH THE SUBMITTED PLANS. |
| | PLEASE SEE PLANS INDICATE KITCHEN WORK |
| | ETC, YET APPLICATION MENTIONS BAR ONLY?? |
| | SEE COMMENTS FROM OTHER TRADES, AS PLANS |
| | ALSO INDICATE REMOVAL OF KITCHEN |
| | EQUIPMENT?? |
| | |
| | 4)NOTE: PLEASE SEE NOT ON PLANS MENTIONS |
| | ALL RECEPTS WITH IN"6" INCHES (") OF |
| | SINKS SHALL BE GFI? |
| | PLEASE SEE 2002 NEC 210.8B3 ETC FOR |
| | RECEPTS WITH IN 6' (FEET) AND ALL |
| | 15A/20A 125V RECEPTS WITHIN A KITCHEN |
| | SHALL BE GFI/GFI PROTECTED. |
| | |
| | 5)NOTE: PLEASE VERIFY LIGHTING CONTACTOR |
| | BEING REMOVED AND REQUIREMENTS OF FBC |
| | CHAPTER 13, 13-415.1.ABC.1.1, IT DOES |
| | NOT SEEM IT IS PERMITTED TO REMOVE THE |
| | AUTOMATIC MEANS OF LIGHTING SHUT OFF |
| | UNLESS MEETING THE REQUIREMENTS AND |
| | PROVIDING NEW MEANS.?? |
| | |
| | 6)NOTE: PLEASE CLARIFY NEW OR EXSITING |
| | WINDOW RECEPTS ABOVE WINDOWS, 210.62, |
| | 220.12. |
| | |
| | 7)NOTE: PLEASE CLARIFY/SHOW NEW OR |
| | EXISTING SIGN CIRCUIT. 600.5 |
| | |
| | 8)NOTE: PLEASE SHOW ALL CONTINUOUS AND |
| | LARGEST MOTOR LOADS AT 125%. |
| | 215.3,230.42 ETC. |
| | PLEASE SHOW LOAD CALCULATIONS PER NEC. |
| | |
| | 9)NOTE: PLEAS VERIFY OCP FOR FACP IS |
| | SHOWN AS 2POLE 20? |
| | 215.5 |
| | |
| | 10)NOTE: COULD NOT LOCATE A FIXTURE |
| | SCHEDULE TO CORRELATE WITH THE FIXTURES |
| | AS NOTED ON PLANS? |
| | PLEASE SUBMIT. |
| | |
| | ** PLEASE SEE OTHER COMMENTS FROM OTHER |
| | TRADES WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ANY |
| | OLD/VOIDED SHEETS FROM SETS OF PLANS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |