Plan Review Notes
Plan Review Notes For Permit 06020332
Permit Number 06020332
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06020332
 ADD: 213 CLEMATIS ST
 CONT: THOMAAS WILLIAMS CONSTRUCTION
 TEL: (954)802-0723
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) THE PERMIT APPLICATION AND WORK
 DESCRIBED ON PLANS DOES NOT MATCH, THIS
 REVIEW WILL BE COMPLETED WITH THE
 DESCRIPTION OF WORK DESCRIBED ON PLANS.
  
 2) THE DESCRIPTION OF WORK DESCRIBED ON
 THE PLANS IS A LEVEL 2 OF THE EXISTING
 BUILDINGS 2004 FBC. SEC 304.1 LEVEL 2
 ALTERATIONS INCLUDE THE RECONFIGURATION
 OF SPACE, THE ADDITION OR ELIMINATION OF
 ANY DOORS OR WINDOWS, THE
 RECONFIGURATION OR EXTENSION OF ANY
 SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT. ALTERATIONS
 LEVEL 2, CHAPTER 6 OF THE EXISTING
 BUILDING FBC SHALL APPLY.
  
 3) PLEASE PROVIDE A CROSS SECTION BOTH
 NORTH / SOUTH AS WELL AS EAST / WEST OF
 THE SO CALLED MEZZANINE LEVEL FOR
 CLARIFICATION. PLEASE PROVIDE ELEVATIONS
  
 FLOOR TO CEILING MEASUREMENTS TO BE
 INCLUDED.
  
 3A) MEZZANINE VS SECOND STORY SEE
 DEFINITION OF MEZZANINE MUST COMMUNICATE
 WITH THE ROOM IT IS IN. IT APPEARS THERE
 IS A WALL DIVIDING THE FRONT OF THE
 BUILDING WITH THE REAR PORTION MAKING IT
  
 A SECOND STORY AND NOT A MEZZANINE.
 SEESEE 2004 FBC SECTION 502 DEFINITIONS:
  
 MEZZANINE. AN INTERMEDIATE LEVEL OR
 LEVELS BETWEEN THE FLOOR AND CEILING OF
 ANY STORY WITH AN AGGREGATE FLOOR AREA
 OF NOT MORE THAN ONE-THIRD OF THE AREA
 OF THE ROOM OR SPACE IN WHICH THE LEVEL
 OR LEVELS ARE LOCATED (SEE SECTION 505
 ).
  
 HEIGHT, STORY. THE VERTICAL DISTANCE
 FROM TOP TO TOP OF TWO SUCCESSIVE
 FINISHED FLOOR SURFACES; AND, FOR THE
 TOP MOST STORY, FROM THE TOP OF THE
 FLOOR FINISH TO THE TOP OF THE CEILING
 JOISTS OR, WHERE THERE IS NOT A CEILING,
 TO THE TOP OF THE ROOF RAFTERS.
  
 1208.2 MINIMUM CEILING HEIGHTS.
 OCCUPIABLE SPACES, HABITABLE SPACES AND
 CORRIDORS SHALL HAVE A CEILING HEIGHT OF
 NOT LESS THAN 7 FEET 6 INCHES (2286 MM).
 BATHROOMS, TOILET ROOMS, KITCHENS,
 STORAGE ROOMS AND LAUNDRY ROOMS SHALL BE
 PERMITTED TO HAVE A CEILING HEIGHT OF
 NOT LESS THAN 7 FEET (2134 MM).
  
 3B)2004 FBC EXISTING BUILDINGS 605.4
 EGRESS DOORWAYS.
 EGRESS DOORWAYS IN ANY WORK AREA SHALL
 COMPLY WITH SECTIONS 605.4.1 THROUGH
 605.4.5 .
  
 3C) 2004 FBC EXISTING BUILDING 605.4.2
 DOOR SWING.
 IN THE WORK AREA AND IN THE EGRESS PATH
 FROM ANY WORK AREA TO THE EXIT
 DISCHARGE, ALL EGRESS DOORS SERVING AN
 OCCUPANT LOAD GREATER THAN 50 SHALL
 SWING IN THE DIRECTION OF EXIT TRAVEL.
  
  
 3D) 2004 EXISTING BUILDING FBC 603.2.3
 SUPPLEMENTAL STAIRWAY ENCLOSURE
 REQUIREMENTS.
 WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS
 THAT ARE PART OF THE MEANS OF EGRESS
 SERVING THE WORK AREA SHALL, AT A
 MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT
 CONSTRUCTION ON THE HIGHEST WORK AREA
 FLOOR AND ALL FLOORS BELOW.
 PROVIDE A SECTION THROUGH STAIRWAY
 INDICATING SHAFT CONSTRUCTIONAND THE
 LOCATION OF THE WOMENS HANDICAPPED
 RESTROOM DOORWAY .
  
 3E) 2004 EXISTING BUILDING 603.4
 INTERIOR FINISH.
 THE INTERIOR FINISH OF WALLS AND
 CEILINGS IN EXITS AND CORRIDORS IN ANY
 WORK AREA SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING .
  
 3F) 2004 EXISTING BUILDING 607.4
 EXISTING STRUCTURAL MEMBERS.
 EXISTING STRUCTURAL COMPONENTS
 SUPPORTING ADDITIONAL EQUIPMENT OR
 SUBJECTED TO ADDITIONAL LOADS BASED ON
 FLORIDA BUILDING CODE, BUILDING, TABLES
 1607.1 AND 1607.6 AS A RESULT OF A
 RECONFIGURATION OF SPACES SHALL COMPLY
 WITH SECTIONS 607.4.1 THROUGH 607.4.3.
  
 607.4.1 GRAVITY LOADS.
 EXISTING STRUCTURAL ELEMENTS SUPPORTING
 ANY ADDITIONAL GRAVITY LOADS AS A RESULT
 OF ADDITIONAL EQUIPMENT OR SPACE
 RECONFIGURATION SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING .
  
 3G) PLANS DO NOT IDENTIFY DOORWAYS WITH
 ALPHA OR NUMERIC CHARACTERS, FIRST FLOOR
 DOORWAY IT APPEARS TO BE A FREEZER DOOR.
 2004 FBC 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF AN
 AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE,
 CORRIDOR, PASSAGEWAY OR LANDING, WHEN
 FULLY OPEN. DOORS SHALL NOT OPEN
 IMMEDIATELY ONTO A STAIR WITHOUT A
 LANDING. THE LANDING SHALL HAVE A WIDTH
 AT LEAST EQUAL TO THE WIDTH OF THE DOOR.
  
 3H) DOORWAY JUST RIGHT OF THE FIRST
 FLOOR FREEZER, ELEC SHEETS INDICATE ICE
 MACHINES;
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3I) BOTH EXISTING RESTROOM DOORS SCALE
 TO BE 2'-0" DOORS , 2004 EXISTING
 BUILDING CODE 605.4 EGRESS DOORWAYS IN
 ANY WORK AREA SHALL COMPLY WITH SECTIONS
 605.4.1 THROUGH 605.4.5.
 2004 FBC 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING
 SHALL BE SUFFICIENT FOR THE OCCUPANT
 LOAD THEREOF AND SHALL PROVIDE A CLEAR
 WIDTH OF NOT LESS THAN 32 INCHES (813
 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH
 THE DOOR OPEN 90 DEGREES (1.57 RAD).
 2004 FBC11-4.1.6(2) DUTY TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO
 ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20 % OF
 THE COST OF THE ALTERA- TION TO THE
 PRIMARY FUNCTION AREA.(A)(I) AN
 ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 4) COVER SHEET NOTE ESIXTING
 CONSTRUCTION BUILDING TYPE ?
 UNKNOWN?NOTE 4C IS REQUIRED BEFORE A
 PERMIT WILL BE ISSUED. SOME EXPLORATION
 ON THE CONTRACTORS PART MAY BE
 NECCESSARY TO DETERMINE MINIMUM BUILDING
 TYPE.
 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 5) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE 713.13(2) IF WORK HAS NOT BEEN
 STARTED AFTER RECORDING OF NOC IT
 BECOMES VOID REQUIRING RE-RECORDING.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026