Plan Review Notes
Plan Review Notes For Permit 06020320
Permit Number 06020320
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-13 00:00:00DENIED
  
 1)NEW DOOR MUST COMPLY WITH FAIR HOUSING
 REQUIREMENTS. USEABLE DOORS MUST PROVIDE
 A NOMINAL 32" CLEAR OPENING OF AT LEAST
 31-5/8 INCHES CLEAR.
  
 2) SPECIFY THE MATERIAL THAT WILL BE
 USED TO FRAME THE INTERIOR WALLS.
 PARTITIONS MUST BE CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS. FBC 603
  
 3) A MECHANICAL PERMIT WIL BE REQUIRED
 TO PROVIDE FOR RETURN AIR FROM THE
 DEN/STUDY WHEN THE OPENING IS ENCLOSED
 BY A WALL AND DOOR.
  
 4) ELECTRICAL CODE REQUIRES SMOKE
 DETECTORS AND ARC FAULT PROTECTED
 CIRCUITS IN BEDROOMS.
  
 5) INTERIOR WALL AND FLOOR FINISHES
 SHALL COMPLY WITH CHAPTER 8 OF THE 2004
 FBC.
  
 6) THIS PROJECT IS LOCATED IN AN R2
 CONDO AND NOT AN R3 ONE OR TWO FAMILY
 RESIDENCE AND DOES NOT QUALIFY FOR THE
 OWNER BUILDER EXCEPTION, THEREFORE, A
 LICENSED CONTRACTOR IS REQUIRED TO PULL
 A PERMIT FOR THIS PROJECT. SEE ATTACHED
 COPY OF STATE STATUTE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714