| 2006-02-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING |
| | INFORMATION REQUIRED FOR PLAN REVIEW: |
| | |
| | 1. RESIDENTIAL (ONE AND TWO FAMILY) |
| | PER 601.3.5.4, SUBMIT A PLUMBING |
| | SANITARY ISOMETRIC RISER DIAGRAM |
| | INDICATING ALL WASTE, VENTS, AND TRAPS |
| | WITH SIZES. |
| | 2. SECTION 405 INSTALLATION OF FIXTURES |
| | 405.3.1 WATER CLOSETS, LAVATORIES SHALL |
| | NOT BE SET CLOSER THAN 15" FROM ITS |
| | CENTER TO ANY SIDE WALL.(NOTE: FINISHED |
| | SIDE WALL OR SHOWER STALL WALL) WATER |
| | CLOSET COMPARTMENTS SHALL NOT BE LESS |
| | THAN 30" WIDE. THERE SHALL BE AT LEAST |
| | 21" CLEARENCE IN FRONT OF LAVATORY OR |
| | WATER CLOSET TO ANY WALL, FIXTURE OR |
| | DOOR. |
| | 417.4 SHOWER COMPARTMENTS. ALL SHOWER |
| | COMPARTMENTS SHALL HAVE A MINIMUM OF 900 |
| | SQUARE INCHES OF INTERIOR |
| | CROSS-SECTIONAL AREA. SHOWER |
| | COMPARTMENTS SHALL NOT BE LESS THAN 30 |
| | INCHES IN MINIMUM DIMENSION MEASURED |
| | FROM THE FINISHED INTERIOR DIMENSION OF |
| | THE COMPARTMENT. |
| | (NOTE: THE ABOVE MEASUREMENTS NEED TO BE |
| | INDICATED ON DRAWING. THE 5 FOOT INSIDE |
| | TO INSIDE MEASUREMENT ON YOUR DRAWING |
| | WILL NOT MEET MINIMUM REQUIREMENTS |
| | PLEASE REWORK MEASUREMENTS TO COMPLY |
| | WITH MINIMUM STANDARDS.) |
| | 3. SECTION 917 AIR ADMITTANCE VALVES. |
| | PLEASE CORRECT DRAWING FROM STUDIO VENT |
| | TO AIR ADMITTANCE VALVE. |
| | |
| | END OF COMMENTS: |
| | |