Plan Review Notes
Plan Review Notes For Permit 06020280
Permit Number 06020280
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-06 00:00:00REDLINED PLANS:
  
 ** CWP TO BE PART OF GE SYSTEM, 250.50
  
 ** REMOVE THE EQUIPMENT GROUNDING
 CONDUCTOR SHOWN IN PICTURES SUBMITTED.
 PLEASE SEE 250.6, 250.24, THE EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.