| 2006-03-22 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)ONLY ONE PHOTOCOPY SITE PLAN WAS |
| | SUBMITTED.TWO SIGNED, SEALED AND DATED |
| | ORIGINALS REQUIRED. FS481.306, |
| | FAC61G10-11.010 |
| | |
| | 2.) STRUCTURES APPEAR IN THE AREA WHERE |
| | THE "TOT LOT" IS TO BE INSTALLED.IT |
| | APPEARS TO GO THROUGH THE CORNER OF WHAT |
| | APPEARS TO BE A BUILDING.CLARIFY SCOPE |
| | OF WORK AND LOCATION. |
| | |
| | 3.)SHOW THE ACCESSIBLE ROUTE TO THE |
| | NEW AMENITY, FBC 11 FAIR HOUSING |
| | ACCESSIBLE GUIDELINES.SHOW WIDTH AND |
| | MAXIMUM SLOPE. |
| | |
| | 4.)THE STRUCTURAL SHEET WAS SEALED BUT |
| | LACKS A TITLE BLOCK FAC61G15-23.002. |
| | THE SEAL IS EXPIRED; SAYS "CERTIFICATE" |
| | RATHER THAN "LICENSE". |
| | |
| | 5.)THE SHEET MARKED J-00918 IN THE TOP |
| | LEFT CORNER STATES THAT THIS DESIGN WILL |
| | MEET ADA GUIDELINES, BUT THE NOTE |
| | DIRECTLY BELOW IT STATES THAT IT DOES |
| | NOT.PLEASE SEE ADAAG GUIDELINES FOR |
| | PLAY AREAS.THESE GUIDELINES ARE NOT AN |
| | ENFORCEABLE STANDARD.HOWEVER, OWNER IS |
| | ADVISED OF THE FOLLOWING, FROM THE ADA |
| | WEBSITE: |
| | |
| | "THE ABSENCE OF SPECIFIC PROVISIONS IN |
| | THE CURRENT STANDARDS DOES NOT MEAN THAT |
| | FACILITIES OR PLAY AREAS ARE EXEMPT FROM |
| | THE PROVISION OF ACCESS; RATHER, IT |
| | MEANS FACILITIES AND AREAS ARE NOT HELD |
| | TO A SPECIFIC LEVEL OF ACCESS UNDER THE |
| | CURRENT STANDARD." |
| | |
| | 6.)OTHER STRUCTURAL SHEETS ARE |
| | CONTAINED IN THE PAPERWORK SUBMITTED BUT |
| | ARE NOT SIGNED AND SEALED.DESIGNER IS |
| | TO SIGN, SEAL, AND DATE ALL STRUCTURAL |
| | ITEMS. |