| Plan Review Notes For Permit 06020260 |
| Permit Number |
06020260 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-03 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PERMIT: | | | | | | 1. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H).(NEED DETAILS OF TANK | | | ANCHORING, ANODE PROTECTION, AND U/G | | | COATING PROTECTION ) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX(561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 | | | |
|