Plan Review Notes
Plan Review Notes For Permit 06020258
Permit Number 06020258
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-23 09:21:17 
  
 REVISION DENIED/INCOMPLETE INFORMATION.
  
 THE RISER NOW HAS TWO ATS SERVING TWO 200 AMP PANELS.
 BECAUSE OF THE SYSTEM CHANGE THE FOLLOWING IS
 REQUIRED.
  
 1} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. THE RISER NOW HAS
 TWO ATS SERVING TWO 200 AMP PANELS.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL(S). 106.3.5.4 FBC AS
 AMENDED.
  
 3} THE PERMITTED GENERATOR WAS A 40 KW. THE REVISION
 INDICATES A 45KW. IF A GENERATOR OTHER THAN THE ONE ON
 THE PERMITTED SET OF PLANS IS TO BE INSTALLED, SUBMIT
 SPECIFICATIONS FOR SAME,
  
 4} PROVIDE SPECIFICATIONS FOR THE ADDED TRANSFER
 SWITCH.
  
 5} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 6} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING,
 AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]