| | FBC 2004 PLUMBING CODE PLAN |
| | REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE |
| | |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | |
| | |
| | DENIED |
| | |
| | |
| | |
| | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION |
| | 106.3.5). |
| | |
| | |
| | |
| | |
| | |
| | |
| | 1) NOTE: THE LETTER SUBMITTED FROM THE MANUFACTURE |
| | DATED 12/6/06 DOES NOT SPECIFY THE MINIMUM CLEARANCE |
| | ALLOAWANCE FOR THIS SPECIFIC SITE ADDRESS. THE MINIMUM |
| | CLEARANCES WILL NOT BE DETEREMINED BY THE AUTHORITY |
| | HAVING JURISDICTION. |
| | PLEASE SUBMIT A "SITE SPECIFIC" LETTER FROM A FLORIDA |
| | REGISTERED ENGINEER ACCEPTING AND STATING THE MINIMUM |
| | CLEARANCE AS LOCATED ON JOBSITE. |
| | IT IS THE DETERMINATION AND UNDERSTANDING FROM THIS |
| | REVIEWER THAT CITY OF WEST PALM BEACH WILL NOT BE |
| | RESPONSIBLE FOR THE "SUFFICIENT ROOM" ALLOWANCES. |
| | THIS SHALL BE EITHER STATED AND/OR DETERMINED BY THE |
| | MANUFACTURE OR BY THE ENGINEER AS STATED ABOVE. |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY |
| | ALSO AFFECT THIS REVIEW OF THE SUBMITTED LETTER. |