Plan Review Notes
Plan Review Notes For Permit 06020258
Permit Number 06020258
Review Stop G
Sequence Number 2
Notes
Date Text
2006-12-20 15:19:25 
 PAUL SCHMITZ
  
 561-805-6692
 [email protected]
 FBC 2004 PLUMBING CODE PLAN
 REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 DENIED
  
  
  
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
  
  
  
  
  
 1) NOTE: THE LETTER SUBMITTED FROM THE MANUFACTURE
 DATED 12/6/06 DOES NOT SPECIFY THE MINIMUM CLEARANCE
 ALLOAWANCE FOR THIS SPECIFIC SITE ADDRESS. THE MINIMUM
 CLEARANCES WILL NOT BE DETEREMINED BY THE AUTHORITY
 HAVING JURISDICTION.
 PLEASE SUBMIT A "SITE SPECIFIC" LETTER FROM A FLORIDA
 REGISTERED ENGINEER ACCEPTING AND STATING THE MINIMUM
 CLEARANCE AS LOCATED ON JOBSITE.
 IT IS THE DETERMINATION AND UNDERSTANDING FROM THIS
 REVIEWER THAT CITY OF WEST PALM BEACH WILL NOT BE
 RESPONSIBLE FOR THE "SUFFICIENT ROOM" ALLOWANCES.
 THIS SHALL BE EITHER STATED AND/OR DETERMINED BY THE
 MANUFACTURE OR BY THE ENGINEER AS STATED ABOVE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 ALSO AFFECT THIS REVIEW OF THE SUBMITTED LETTER.
 QUESTIONS