| Plan Review Notes For Permit 06020239 |
| Permit Number |
06020239 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-09 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PERMIT: | | | | | | 1. GAS PIPING SYSTEM IS SIZED | | | INCORRECTLY PLEASE SIZE CORRECT USING | | | THE FOLLOWING TABLES FROM THE FBC-2004 | | | FUEL GAS CODE. | | | SCHEDULE 40 METALLIC PIPE - 402.4(2) | | | CSST - 402.4(14) | | | CSST - FOR GASTITE TABLE 7.1 FROM THE | | | GASTITE INSTALLATION MANUAL. | | | CSST - TRACKPIPE HAS NO MATCHING TABLE | | | POLYETHYLENE PLASTIC PIPE - 402.4(20) | | | 2. GALVANIZED PIPE UNDERGROUND NOT | | | ALLOWED. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX(561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 |
|