Plan Review Notes
Plan Review Notes For Permit 06020194
Permit Number 06020194
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT A LOAD CALCULATION PER
 230.31. THE ENTIRE SERVICE, EXISTING AND
 NEW.
  
 2} SUBMIT A PANEL SCHEDULE FOR "MDP".
 INDICATE RATING, VOLTS/AMPS. 215.5.
  
 3} SUBMIT A PANEL SCHEDULE FOR PANEL
 "A".
  
 4} PLEASE VERIFY NOTE #1 FPL FEEDER
 SIZE. THEY DON'T DOWNSIZE THE NEUTRAL
 CONDUCTOR.
  
 5} PLEASE SEE THE CONDUCTORS IN THE
 NIPPLE FEEDING THE 400 AMP MDP DO NOT
 COMPLY WITH 310.15. THERE SHOULD NOT BE
 A GROUND WITH THE NEUTRAL UNTILL THE
 NEUTRAL IS ISOLATED AT THE FIRST MEANS
 OF DISCONNECT. SEE 250.6.
  
 6} INDICATE THE AMPERAGE RATING OF ALL
 PANELS.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718