| Plan Review Notes For Permit 06020194 |
| Permit Number |
06020194 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-14 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT A LOAD CALCULATION PER | | | 230.31. THE ENTIRE SERVICE, EXISTING AND | | | NEW. | | | | | | 2} SUBMIT A PANEL SCHEDULE FOR "MDP". | | | INDICATE RATING, VOLTS/AMPS. 215.5. | | | | | | 3} SUBMIT A PANEL SCHEDULE FOR PANEL | | | "A". | | | | | | 4} PLEASE VERIFY NOTE #1 FPL FEEDER | | | SIZE. THEY DON'T DOWNSIZE THE NEUTRAL | | | CONDUCTOR. | | | | | | 5} PLEASE SEE THE CONDUCTORS IN THE | | | NIPPLE FEEDING THE 400 AMP MDP DO NOT | | | COMPLY WITH 310.15. THERE SHOULD NOT BE | | | A GROUND WITH THE NEUTRAL UNTILL THE | | | NEUTRAL IS ISOLATED AT THE FIRST MEANS | | | OF DISCONNECT. SEE 250.6. | | | | | | 6} INDICATE THE AMPERAGE RATING OF ALL | | | PANELS. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|