| Plan Review Notes For Permit 06020194 |
| Permit Number |
06020194 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-17 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT A LOAD CALCULATION PER | | | 230.31 | | | | | | 2} SUBMIT A PANEL SCHEDULE FOR "MDP". | | | INDICATE RATING, VOLTS/AMPS. 215.5. | | | | | | 3} SUBMIT A PANEL SCHEDULE FOR PANEL | | | "A". | | | | | | 4} PLEASE VERIFY NOTE #1 FPL FEEDER | | | SIZE. THEY DON'T DOWNSIZE THE NEUTRAL | | | CONDUCTOR. | | | | | | 5} PANEL AND METER LOCATION (SHEET E1.1) | | | MUST COMPLY WITH 110.26 CLEARANCE | | | REQUIREMENTS. | | | | | | 6} THE RECEPTACLE SPCING FOR KITCHEN | | | COUNTERTOPS MUST COMPLY WITH 210.52(C). | | | SEE REVIEWED SET OF PLANS FOR AREAS IN | | | QUESTION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|