2006-04-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS REVIEW
  
  
 _XX_4.COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE OR PROVIDE
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.YOU MAY SHOW ANCHOR SPACING BY
 CIRCLING IT ON THE APPROPRIATE CHARTS ON
 THE PRODUCT APPROVAL.THE FORM
 SUBMITTED IS INCOMPLETE, DOES NOT SHOW
 ANCHOR SPACING OR INDICATE HORIZONTAL OR
 VERTICAL INSTALLATION.
  
 _XX_5.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72,
 WWW.FLORIDABUILDING.ORG.
 ALSO THE DOCUMENTS SUBMITTED WERE
 ILLEGIBLE.SUBMIT TWO COPIES OF LEGIBLE
 DOCUMENTS.ALL DOCUMENTS SUBMITTED ARE
 ILLEGIBLE.CODE COMPLIANCE CANNOT BE
 DETERMINED.
  
 _XX_6.ON THE PRODUCT APPROVAL, MARK
 WHICH DETAILS APPLY TO THIS JOB.PLEASE
 USE INK RATHER THAN A HIGHLIGHTER.
  
 _XX_8.PROVIDE A FLOOR PLAN SHOWING
 WHERE THE SHUTTERS WILL BE INSTALLED
 WHICH CORRELATES WITH THE INSTALLATION
 SCHEDULE, ITEM 4 ABOVE.
  
 _XX_ 9.PROVIDE A DETAIL SHOWING HOW
 YOU WILL BE PREPARING THE OPENING
 STRUCTURALLY FOR THE DOOR, FBC16.
  