| 2006-04-12 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | FROM PREVIOUS REVIEW |
| | |
| | |
| | _XX_4.COMPLETE THE ATTACHED |
| | INSTALLATION SCHEDULE OR PROVIDE |
| | REQUIRED INFORMATION IN A SIMILAR |
| | FORMAT.YOU MAY SHOW ANCHOR SPACING BY |
| | CIRCLING IT ON THE APPROPRIATE CHARTS ON |
| | THE PRODUCT APPROVAL.THE FORM |
| | SUBMITTED IS INCOMPLETE, DOES NOT SHOW |
| | ANCHOR SPACING OR INDICATE HORIZONTAL OR |
| | VERTICAL INSTALLATION. |
| | |
| | _XX_5.FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72, |
| | WWW.FLORIDABUILDING.ORG. |
| | ALSO THE DOCUMENTS SUBMITTED WERE |
| | ILLEGIBLE.SUBMIT TWO COPIES OF LEGIBLE |
| | DOCUMENTS.ALL DOCUMENTS SUBMITTED ARE |
| | ILLEGIBLE.CODE COMPLIANCE CANNOT BE |
| | DETERMINED. |
| | |
| | _XX_6.ON THE PRODUCT APPROVAL, MARK |
| | WHICH DETAILS APPLY TO THIS JOB.PLEASE |
| | USE INK RATHER THAN A HIGHLIGHTER. |
| | |
| | _XX_8.PROVIDE A FLOOR PLAN SHOWING |
| | WHERE THE SHUTTERS WILL BE INSTALLED |
| | WHICH CORRELATES WITH THE INSTALLATION |
| | SCHEDULE, ITEM 4 ABOVE. |
| | |
| | _XX_ 9.PROVIDE A DETAIL SHOWING HOW |
| | YOU WILL BE PREPARING THE OPENING |
| | STRUCTURALLY FOR THE DOOR, FBC16. |
| | |