| Plan Review Notes For Permit 06020143 |
| Permit Number |
06020143 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-02-09 00:00:00 | SECOND REVIEW | | | | | | 1) SUBMIT THE SHEETS FROM THE POLYGLASS | | | MODIFIED BITUMEN SYSTEM NOA THAT SPECIFY | | | THE APPROVED ASSEMBLY THAT WILL BE | | | INSTALLED. THE DESIGN PRESSURES FOR THE | | | ASSEMBLY ARE LISTED ON THESE SHEETS. | | | | | | 2) THIS NOA (#03-0130.08) FOR FL985-R1 | | | REQUIRES ENHANCED FASTENING CALCULATIONS | | | USING RAS 117 TO BE PREPARED, SIGNED AND | | | SEALED BY A FLORIDA REGISTERED ENGINEER, | | | ARCHITECT OR REGISTERED ROOF CONSULTANT. | | | READ LIMITATION #7 ON PAGE 45 ON NOA. | | | | | | 3) IF LIMITATION #9 IS SPECIFIED AT THE | | | DESIGN PRESSURE LISTED FOR THE ASSEMBLY | | | THEN NO INCREASE IN PRESSURES ARE | | | ALLOWED. SEE LIMITATION #9 ON PAGE 45 OF | | | THE NOA. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | |
|