2006-03-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06020129
 ADD: 1801 PALM BCH LAKES# 230C
 CONT:PLAN REVIEW
 GENERAL GROWTH C/O ASHLEY
 STEWART
 TEL: (201)319-9093
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) SHEET T1.0 CODE INFORMATION
 1A)COMPLIED.
 1B)COMPLIED.
 1C)COMPLIED.
 1D) ALL CODE REFRENCES AND TABLES ARE
 NOT 2004 FBC.
 THE NEW T1.0 SHEET INDICATESTHE NEW
 TABLE 601 FOR BUILDING CLASSIFICATION,
 BUT THE WRONG BUILDING TYPE. PLANS
 INDICATE A TYPE IV BUILDING WHICH UNDER
 THE 2004 CODE IS HEAVY TIMBER.
  
  
 2) A1.0 & A2.0 THE REAR EGRESS DOES NOT
 MEET THE MANEUVERING CLEARENCES OF A
 DOOR 12" REQUIRED PUSH SIDE OF LATCH
 WHEN A DOOR CLOSER AND LATCH ARE
 PRESENT.11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3)COMPLIED.
  
 NEW COMMENTS DUE TO THE REDESIGN OF THE
 FLOOR PLAN.
  
 4) THE EGRESS PATH FROM THE FRONT OF THE
 STORE TO THE STORAGE AREA, THE DOORWAY
 THAT ENTERS THE STOREROOM DOES NOT MEET
 THE MANEUVERING CLEARENCES. 11-4.13.6
 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 5) DRESSING ROOMS VERSES DOOR SWING.
 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF AN
 AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE,
 CORRIDOR, PASSAGEWAY OR LANDING, WHEN
 FULLY OPEN. DOORS SHALL NOT OPEN
 IMMEDIATELY ONTO A STAIR WITHOUT A
 LANDING. THE LANDING SHALL HAVE A WIDTH
 AT LEAST EQUAL TO THE WIDTH OF THE DOOR.
 THE SECOND ISSUE IS THAT IT APPEARS THAT
 THE HANDICAPPED DRESSING ROOM IS THE
 ROOM BEHIND THE COMMON DRESSING ROOM
 MAKING IT HARDER FOR TURNING AND ALSO
 ACCESSIBLITY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026