| Date |
Text |
| 2006-06-01 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FLORIDA ADMINITRATIVE CODE |
| | FLORIDA STATUTES |
| | MUNICIPAL CODE WPB |
| | |
| | 1. TWO APPLICATIONS SUBMITTED FOR |
| | SEPARATE PARKING GARAGES, BUT NEITHER |
| | INDICATE WHICH PERMIT APPLICATION IS FOR |
| | WHICH PARKING GARAGE. SEPARATE PLANS ARE |
| | REQUIRED FOR EACH PERMIT. (THREE SETS OF |
| | PLANS EACH). SECTION106.1. |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. INFORMATION |
| | REQUIRED FOR TITLE BLOCK NOT SHOWN: FAC |
| | 61G1-16.004(6) PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. FS |
| | 481.2055. |
| | |
| | 3. SHTS A1.6 & A1.12 SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS. |
| | INDICATE SQUARE FOOTAGE FOR EACH DRAIN, |
| | ALONG WITH 1/2 AREA OF ALL VERTICAL |
| | WALLS INCLUDING PARAPETS. SHOW THE SF OF |
| | ALL ROOF AREAS THAT DRAIN ONTO THE ROOF |
| | FROM ABOVE. SECTIONS 1106 & 1107 WITH |
| | ALL SUBSECTIONS. |
| | |
| | 4. SHTS A1.6 & A1.12 INDICATE THE |
| | LOCATION OF ALL SECONDARY ROOF DRAINS. |
| | THE RAMPS WILL TAKE THE OVERFLOW FROM |
| | THE SOUTH SIDE OF THE 6TH FLOOR, BUT THE |
| | NORTH SIDE SHOWS NO SECONDARY ROOF |
| | DRAINS. PLEASE INDICATE ON PLANS. |
| | SECTION 106.1.1. |
| | |
| | 5. SHT P2.0S DETENTION POND INDICATE |
| | INLET PIPING, BUT NO DISCHARGE PIPING |
| | SHOWN. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 6. SHT P2.OS PLEASE SHOW THE SQUARE |
| | FOOTAGE BEING DRAINED BY EACH STORM |
| | DRAIN LINE TO THE DETENTION POND. TABLE |
| | 1106.3. |
| | |
| | 7. SHT P2.OS PLEASE INDICATE WHAT THE |
| | TWO 2" LINES TO THE DETENTION POND IS |
| | DRAINING. (SHOWS 2" HUB DRAINS ON SHT |
| | P2.1S). SECTION 106.1.1. |
| | |
| | 8. SHT P2.1S 4"AD IN FIRE PUMP ROOM |
| | SHALL CONNECT TO SANITARY SYSTEM. |
| | SECTION 90-203 MUNICIPAL CODE. |
| | |
| | 9. P2.1S INDICATES DOMESTIC WATER PUMP. |
| | NO INFORMATION SUBMITTED FOR PUMP ROOM. |
| | SUBMIT MANUF. SPECIFICATION FOR PUMP/S. |
| | PUMP/S SHALL BE LISTED. SUBMIT A DETAIL |
| | FOR THE PUMP ROOM SHOWING ALL PIPING, |
| | PIPE SIZES, VALVES ETC. SECTIONS 106.1.1 |
| | & 303.4 |
| | |
| | 10. SUBMIT STORM RISER DIAGRAMS SHOWING |
| | ALL PIPE SIZES, SF DRAINED BY EACH RISER |
| | AND SHOW ALL OFFSETS IF APPLICABLE. |
| | SECTION 106.3.5.1.3. |
| | |
| | 11. SUBMIT A WATER RISER DIAGRAM FOR THE |
| | DOMESTIC PUMP ROOM WATER SYSTEM. SHOW |
| | ALL PIPE SIZE, VALVES ETC. SECTION |
| | 106.3.5.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |