Plan Review Notes
Plan Review Notes For Permit 06020120
Permit Number 06020120
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-01 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINITRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
 1. TWO APPLICATIONS SUBMITTED FOR
 SEPARATE PARKING GARAGES, BUT NEITHER
 INDICATE WHICH PERMIT APPLICATION IS FOR
 WHICH PARKING GARAGE. SEPARATE PLANS ARE
 REQUIRED FOR EACH PERMIT. (THREE SETS OF
 PLANS EACH). SECTION106.1.
  
 2. ALL ARCHITECTURAL SHEETS. INFORMATION
 REQUIRED FOR TITLE BLOCK NOT SHOWN: FAC
 61G1-16.004(6) PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT. FS
 481.2055.
  
 3. SHTS A1.6 & A1.12 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 INDICATE SQUARE FOOTAGE FOR EACH DRAIN,
 ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS. SHOW THE SF OF
 ALL ROOF AREAS THAT DRAIN ONTO THE ROOF
 FROM ABOVE. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS.
  
 4. SHTS A1.6 & A1.12 INDICATE THE
 LOCATION OF ALL SECONDARY ROOF DRAINS.
 THE RAMPS WILL TAKE THE OVERFLOW FROM
 THE SOUTH SIDE OF THE 6TH FLOOR, BUT THE
 NORTH SIDE SHOWS NO SECONDARY ROOF
 DRAINS. PLEASE INDICATE ON PLANS.
 SECTION 106.1.1.
  
 5. SHT P2.0S DETENTION POND INDICATE
 INLET PIPING, BUT NO DISCHARGE PIPING
 SHOWN. PLEASE CLARIFY. SECTION 106.1.1.
  
 6. SHT P2.OS PLEASE SHOW THE SQUARE
 FOOTAGE BEING DRAINED BY EACH STORM
 DRAIN LINE TO THE DETENTION POND. TABLE
 1106.3.
  
 7. SHT P2.OS PLEASE INDICATE WHAT THE
 TWO 2" LINES TO THE DETENTION POND IS
 DRAINING. (SHOWS 2" HUB DRAINS ON SHT
 P2.1S). SECTION 106.1.1.
  
 8. SHT P2.1S 4"AD IN FIRE PUMP ROOM
 SHALL CONNECT TO SANITARY SYSTEM.
 SECTION 90-203 MUNICIPAL CODE.
  
 9. P2.1S INDICATES DOMESTIC WATER PUMP.
 NO INFORMATION SUBMITTED FOR PUMP ROOM.
 SUBMIT MANUF. SPECIFICATION FOR PUMP/S.
 PUMP/S SHALL BE LISTED. SUBMIT A DETAIL
 FOR THE PUMP ROOM SHOWING ALL PIPING,
 PIPE SIZES, VALVES ETC. SECTIONS 106.1.1
 & 303.4
  
 10. SUBMIT STORM RISER DIAGRAMS SHOWING
 ALL PIPE SIZES, SF DRAINED BY EACH RISER
 AND SHOW ALL OFFSETS IF APPLICABLE.
 SECTION 106.3.5.1.3.
  
 11. SUBMIT A WATER RISER DIAGRAM FOR THE
 DOMESTIC PUMP ROOM WATER SYSTEM. SHOW
 ALL PIPE SIZE, VALVES ETC. SECTION
 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  