| Date |
Text |
| 2006-04-10 00:00:00 | DENIED:ENCLOSED GARAGE / 6 LEVELS |
| | |
| | 1.SEE COMMENT #3 BY DEWEY PALMER, |
| | ELECTRICAL PLAN REVIEW; SEAL SHALL |
| | INDICATE "LICENSE NUMBER" NOT |
| | "CERTIFICATE NUMBER" IN ACCORDANCE WITH |
| | FAC 61G15-23.001. |
| | |
| | 2.NO MECHANICAL PLANS SUBMITTED FOR |
| | REVIEW.PLAN SHEET E1.1 INDICATES |
| | EXHAUST FAN SCHEDULE BUT DOES NOT GIVE |
| | CALCULATIONS FOR MAKE UP AIR OR GIVE AIR |
| | CHANGES PER HOUR. |
| | |
| | 3.PLEASE SHOW COMPLIANCE WITH 2004 FMC |
| | 404.2, AUTOMATIC OPERATION OF THE SYSTEM |
| | SHALL NOT REDUCE THE VENTILATION RATE |
| | BELOW 0.05 CFM PER SQUARE FOOT OF THE |
| | FLOOR AREA & THE SYSTEM SHALL BE CAPABLE |
| | OF PRODUCING A VENTILATION RATE OF 1.5 |
| | CFM OF THE FLOOR AREA. |
| | |
| | 4.PER 2004 FMC 404.3 CONNETING |
| | OFFICES, WAITING ROOMS TICKET BOOTHS & |
| | SIMILAR USES THAT ARE ACCESSORY TO A |
| | PUBLIC GARAGE SHALL BE MAINTAINED AT A |
| | POSITIVE PRESSURE AND BE PROVIDED WITH |
| | VENTILATION IN ACCORDANCE WITH 2004 FMC |
| | 403.3. |
| | |
| | 5.PLEASE INDICATE IF THERE WILL BE ANY |
| | PROVISIONS SHOULD LOSS OF POWER OCCUR. |
| | |
| | PLEASE NOTE, PLANS ARE INCOMPLETE |
| | THEREFORE ADDITIONAL COMMENTS MAY BE |
| | GENERATED WITH RESUBMITTAL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |