| 2006-06-14 00:00:00 | ***DENIED*** |
| | |
| | 1) FIRE EXTINGUISHERS ARE SHOWN ON GRADE |
| | LEVEL PLANS. PLEASE SHOW LOCATIONS ON |
| | ALL FLOORS MOUNTED AT DISTANCES NOT TO |
| | EXCEED 75' TRAVEL DISTANCE. |
| | |
| | 2) PLEASE SHOW ALL MAXIMUM TRAVEL |
| | DISTANCES ON LIFE SAFETY PLAN. |
| | |
| | 3) PLEASE PROVIDE MANUFACTURER SPEC |
| | SHEETS FOR FIRE PUMP, GENERATOR AND |
| | ASSOCIATED EQUIPMENT. |
| | |
| | 4) EXIT STAIRS TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 5) SEPARATE SHOP DRAWINS AND PERMITS ARE |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 6) SIGNS ARE REQUIRED IN STAIRWELLS |
| | INDICATING FLOOR IDENTIFICATION, TOP AND |
| | BOTTOM FLOORS AND DIRECTION TO EXIT |
| | DISCHARGE. |
| | |
| | 7) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES (3) STORIES OR |
| | 30' IN HEIGHT. |
| | |
| | 8) ADDRESS NUMBER REQUIRED ON BUILDING. |
| | PLEASE ILLUSTRATE ON ELEVATIONS. |
| | |
| | 9) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENT FOR HANDRAILS AND GUARDS. |
| | |
| | 10) EXITS SIGNS SHALL BE MOUNTED AT |
| | LOCATIONS MAKING THE WAY TO REACH THE |
| | EXIT CLEAR AND OBVIOUS. |
| | |
| | 11) TACTILE SIGNAGE REQUIRED AT EACH |
| | EXIT DOOR THAT COMPLIES WITH NFPA 101, |
| | SEC. 7.10.1.3. |
| | |
| | 12) FIRE DEPARTMENT VALVES SHALL BE 2 |
| | 1/2" TO 1 1/2" REDUCER WITH CHAINS. |
| | |
| | 13) FIRE SPRINKLER LAYOUT NOT SHOWN OF |
| | FIRE PROTECTION SHEETS. |
| | |
| | 14) FIRE ALARM SHALL BE UL CERTIFIED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 15) NO STORAGE ALLOWED IN ROOMS OR AREAS |
| | NOTED FOR SERVICE AND INSPECTIONS. |
| | APPROVED ACCESS SHALL BE PROVIDED TO |
| | FIRE PUMP AND ELECTRICAL ROOM. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |