Plan Review Notes
Plan Review Notes For Permit 06020120
Permit Number 06020120
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-14 00:00:00***DENIED***
  
 1) FIRE EXTINGUISHERS ARE SHOWN ON GRADE
 LEVEL PLANS. PLEASE SHOW LOCATIONS ON
 ALL FLOORS MOUNTED AT DISTANCES NOT TO
 EXCEED 75' TRAVEL DISTANCE.
  
 2) PLEASE SHOW ALL MAXIMUM TRAVEL
 DISTANCES ON LIFE SAFETY PLAN.
  
 3) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR FIRE PUMP, GENERATOR AND
 ASSOCIATED EQUIPMENT.
  
 4) EXIT STAIRS TO BE KEPT UP WITH
 CONSTRUCTION.
  
 5) SEPARATE SHOP DRAWINS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 6) SIGNS ARE REQUIRED IN STAIRWELLS
 INDICATING FLOOR IDENTIFICATION, TOP AND
 BOTTOM FLOORS AND DIRECTION TO EXIT
 DISCHARGE.
  
 7) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES (3) STORIES OR
 30' IN HEIGHT.
  
 8) ADDRESS NUMBER REQUIRED ON BUILDING.
 PLEASE ILLUSTRATE ON ELEVATIONS.
  
 9) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 10) EXITS SIGNS SHALL BE MOUNTED AT
 LOCATIONS MAKING THE WAY TO REACH THE
 EXIT CLEAR AND OBVIOUS.
  
 11) TACTILE SIGNAGE REQUIRED AT EACH
 EXIT DOOR THAT COMPLIES WITH NFPA 101,
 SEC. 7.10.1.3.
  
 12) FIRE DEPARTMENT VALVES SHALL BE 2
 1/2" TO 1 1/2" REDUCER WITH CHAINS.
  
 13) FIRE SPRINKLER LAYOUT NOT SHOWN OF
 FIRE PROTECTION SHEETS.
  
 14) FIRE ALARM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 15) NO STORAGE ALLOWED IN ROOMS OR AREAS
 NOTED FOR SERVICE AND INSPECTIONS.
 APPROVED ACCESS SHALL BE PROVIDED TO
 FIRE PUMP AND ELECTRICAL ROOM.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  