Plan Review Notes
Plan Review Notes For Permit 06020120
Permit Number 06020120
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-31 00:00:00********* UNSAT ************
  
 1) NOTE: PLEASE SEE TWO APPLICATIONS FOR
 TWO SEPARATE PARKING STRUCTURES WERE
 SUBMITTED, HOWEVER ONLY PLANS FOR ONE
 STRUCTURE WERE SUBMITTED. PLEASE KNOW,
 EACH PERMITTED STRUCTURE WILL REQUIRE
 THREE SETS OF SIGNED, DATED AND SEALED
 PLANS.
  
 2) NOTE: PLEASE SEE COMMENTS FROM ALL
 TRADES UNDER THE PERMITS FOR "LOFT
 BUILDINGS" AS EGRESS, EGRESS LIGHTING
 AND FIRE SEPARATIONS SEEM TO CONTAIN
 AREAS OF CONFLICT.
  
 3) NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS WITH RESPECT TO THE SEAL USED
 ON SPC SHEETS. PLEASE SEE FAC
 61G15-23.001 WHICH NO LONGER ACCEPTS THE
 WORDING OF "CERTIFICATE" IN SAID SEAL.
 PLEASE SEE THE RULING WHICH WAS PAST ON
 FEB 4TH, 2004 WAS GRANTED AN EXTENSION
 TO HAVE ALL SEALS CHANGED OUT BY
 12/31/2006 TO WORDING OF "LICENSE" IN
 SAID SEAL.
  
 4) NOTE:PLEASE SEE THE FOLLOWING CODES
 SHALL BE REFLECTED ON PLANS. 2002
 NFPA-70,2001 NFPA-101, 2002 NFPA-72,
 1999 NFPA-20
  
  
 5) NOTE: PLEASE SUBMIT ALL
 SPECIFICATIONS / MANUFACTURES CUT SHEETS
 FOR FIRE PUMP, FIRE PUMP CONTROLLER.
 PLEASE CLARIFY TWO MEANS OF DISCONNECT
 AND OVER CURRENT PROTECTION? PLEASE SEE
 COMMENTARY IN THE NEC HANDBOOK UNDER
 695.4 "TYPICALLY, THE SUPPLY CONDUCTORS
 OF THE POWER SOURCE ARE DIRECTLY
 CONNECTED, WITHOUT A DISCONNECTING MEANS
 OR OVERCURRENT PROTECTION, TO THE FIRE
 PUMP CONTROLLER OR COMBINATION FIRE PUMP
 CONTROLLER AND POWER TRANSFER SWITCH.
 HOWEVER, A SINGLE DISCONNECTING MEANS IS
 ALLOWED, PROVIDED ALL THE CONDITIONS IN
 695.4(B), SUPERVISED CONNECTION, ARE
 MET".
 PLEASE KNOW, LOCKED ROTOR CURRENT FOR
 BOTH LOCATIONS ARE NOT THE NORM, AND THE
 FIRE PUMP CONTROLLER CONTAINS THE OCP,
 ATS, DISCONNECTING MEANS.
 230.76.230.79, 6-3.2.2.1, 7-3.6 NFPA-20
 PLEASE SEE FIRE PUMP MAIN LOCATION
 OUTSIDE WITH GENERAL ACCESS BY THE
 PUBLIC IS NOT PERMITTED PER NFPA-70 695,
 NFPA-20 CHAPTER 6,7 AND AHJ.
 PLEASE DETAIL ENCASEMENT OF FIRE PUMP
 SEC'S ETC NOT CONSIDERED OUTSIDE THE
 BLDG. 240.6
 PLEASE INCLUDE ALL INFORMATION ON
 ELECTRICAL PLANS FOR FIRE PUMP AND
 LOCKED ROTOR. PLEASE INCLUDE HP RATING,
 SETTING FOR LOCKED ROTOR ETC
 215.5
  
 6) NOTE: PLEASE PROVIDE THE GROUNDING
 ELECTRODE CONNECTIONS AND DETAILS.
 PLEASE SEE PLANS MENTIONS SEE NEC 250.
 THE CODE SHALL NOT BE "QUOTED" IN LIEU
 OF DETAIL OR SPECIFIC DESIGN.
 PLEASE SEE 250.50, 250.52, 250.104 ETC
 FOR ALL REQUIRED CONNECTION POINTS.
 PLEASE ALSO SEE "KEYED NOTES" #6 IS
 NOTED FOR GROUNDING ELECTRODE OF MAIN
 SERVICE, HOWEVER THIS NOTE DOES NOT
 CORRELATE WITH WHAT THE GEC SHOULD BE?
  
 7) NOTE: PLEASE SEE PANEL "LD" IS
 REQUIRED TO CONTAIN AND MCB. NO
 EXCEPTIONS PER 230.70, 90.4
  
 8) NOTE: PLEASE SPECIFY THE PANEL LE AND
 LL AS CONTAINING "FEED-THRU" LUGS AS ONE
 PANEL BOARD MAY NOT CONTAIN OVER 42 OCP
 DEVICES. 408.15
  
 9) NOTE: PLEASE PLACE NOTE FOR ALL
 "SIGNAGE" WHICH WILL BE REQUIRED IN A
 MIN OF 1INCH LETTERING ON CONTRASTING
 BACKGROUND DENOTING ALL EQUIPMENT
 LOCATIONS.
 PLEASE SEE FIRE REVIEW NOTES AS LOCATION
 OF FACP MAY BE REQUIRED TO BE RELOCATED.
 PLEASE SEE THAT IN THE NEW LOCATION OF
 THE FACP WILL REQUIRE SIGNAGE AND
 MAPPING OF ALL SERVICE DISCONNECTING
 MEANS, FIRE PUMP, GENERATOR ETC.
 215.5, 230.2, 700.8 ETC
 NFPA-20,-110
  
 10) NOTE: PLEASE SUBMIT SPECS/CUT SHEETS
 FOR GENERATOR.
 PLEASE COMPLETE PLANS FOR GENERATOR AS
 NO INFORMATION, RISER, ETC WAS
 SUBMITTED.
 PLEASE SEE COMMENTS UNDER OTHER BUILDING
 PERMITS FOR INFORMATION.
  
 11) NOTE: PLEASE SEE NFPA-110 7.3.3* FOR
 MINIMUM LIGHTING LEVELS IN GENERATOR
 ROOM. (30 FT CANDLES.
  
 12) NOTE: PLEASE CORRELATE FIXTURE
 SCHEDULE WITH ALL FIXTURES INDICATED ON
 PLANS.
 PLEASE SEE FIX H2, H2E, U-1, U-3,,,
 PLEASE SEE FIXTURES SHOWN ON PLANS, BUT
 NOT ON SCHEDULE.
  
 13) NOTE: PLEASE PROVIDE COMPLETE PHOTO
 METRICS FOR STAIR TOWERS AND GARAGE
 AREAS PATHS FOR EGRESS.
 PLEASE SEE 2003 NFPA-101 7.8.1.3,
 7.9.2.2 WHICH REQUIRES 10FT CANDLES (108
 LUX) IN STAIR TOWERS UNDER NORMAL
 CONDITIONS AND 1 FT CANDLE UNDER
 EMERGENCY CONDITIONS. PLEASE SEE GARAGE
 AREAS REQUIRES 1FT CANDLE UNDER BOTH.
 THESE ARE AVERAGES, AND A TYPICAL DETAIL
 MAY BE PROVIDED FOR STAIRS AND EACH
 FLOOR.
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 14) NOTE: PLEASE PROVIDE ALL AREA AND
 ROOM DESIGNATIONS ON PLANS.
 215.5
 PLEASE SEE SOME AREAS WHERE THERE IS NOT
 INDICATION WHAT ROOMS ARE FOR.
  
 15) NOTE: PLEASE SEE 230.2, 230.70,
 230.72 FOR ALL MAINS AND ELECTRICAL
 SYSTEMS IN BUILDINGS. THIS IS ONE
 BUILDING AND SHALL CONTAIN ONLY ONE
 SERVICE. THE EMERGENCY SERVICE FOR THE
 FIRE PUMP IS PERMITTED UNDER THE
 EXCEPTIONS.
  
 16) NOTE: PLEASE SEE 2004 FBC CHAPTER
 13, 13-415.1.ABC.1.1 AND
 13-415.1.ABC.1.2 FOR CONTROL OF
 LIGHTING. PLEASE KNOW, PARKING GARAGE
 AREAS, EGRESS AREAS WILL NOT BE
 CONSIDERED AS PART OF THESE
 REQUIREMENTS.
 PLEASE INDICATE CONTROL METHODS, TIME
 SCHEDULING ETC.
 PLEASE SEE 13-413.1ABC.1 FOR FEEDERS AND
 BRANCH CIRCUITS. PLEASE PROVIDE VOLTAGE
 DROP CALCULATIONS FOR WORST CASE
 SCENARIO AND/OR DIAGRAM FOR LONGEST
 RUN(S). PLEASE KNOW, THIS IS FOR THE
 RUNS AS NOTED ABOVE, NOT ALL AS MANY
 WILL NOT APPLY.
 PLEASE SEE ALL EXTERIOR LIGHTING SHALL
 BE CONTROL BY ONE OF THE METHODS AS
 LISTED IN 13-415.1.ABC.1.4
  
  
 17) NOTE: PLEASE SEE THAT ALL CONTINUOUS
 LOADS SHOULD BE INDICATED FOR FEEDERS
 ALSO. 215.3, 230.42
  
 18) NOTE: PLEASE INDICATE THE LOCATION
 OF THE GENERATOR ENUNCIATOR PANEL.
  
 19) NOTE: PLEASE SEE ADDRESSING STOP.
 ONCE ADDRESS OF THE TWO GARAGES IS
 CONFIRMED ALL EMERGENCY NOTIFICATION
 SYSTEMS SHALL COMPLY PER FIRE REVIEW
 COMMENTS. PLEASE ALSO ADJUST PLANS,
 TITLE BLOCKS FOR ADDRESS AS "SAIL CLUB"
 NEEDS TO BE MORE SPECIFIC OF THE ACTUAL
 ADDRESS AND LOCATION.
  
 ** PLEASE BE AWARE OF COMMENTS FROM
 OTHER TRADES WHICH WILL HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 ** WHEN RESUBMITTING THE PLANS, PLEASE
 BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO THREE COMPLETE SETS
 FOR EACH PERMIT. PLEASE SUBMIT ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS
 SEPARATELY FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW> IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  