| Date |
Text |
| 2006-03-31 00:00:00 | ********* UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE TWO APPLICATIONS FOR |
| | TWO SEPARATE PARKING STRUCTURES WERE |
| | SUBMITTED, HOWEVER ONLY PLANS FOR ONE |
| | STRUCTURE WERE SUBMITTED. PLEASE KNOW, |
| | EACH PERMITTED STRUCTURE WILL REQUIRE |
| | THREE SETS OF SIGNED, DATED AND SEALED |
| | PLANS. |
| | |
| | 2) NOTE: PLEASE SEE COMMENTS FROM ALL |
| | TRADES UNDER THE PERMITS FOR "LOFT |
| | BUILDINGS" AS EGRESS, EGRESS LIGHTING |
| | AND FIRE SEPARATIONS SEEM TO CONTAIN |
| | AREAS OF CONFLICT. |
| | |
| | 3) NOTE: PLEASE SEE BUILDING REVIEW |
| | COMMENTS WITH RESPECT TO THE SEAL USED |
| | ON SPC SHEETS. PLEASE SEE FAC |
| | 61G15-23.001 WHICH NO LONGER ACCEPTS THE |
| | WORDING OF "CERTIFICATE" IN SAID SEAL. |
| | PLEASE SEE THE RULING WHICH WAS PAST ON |
| | FEB 4TH, 2004 WAS GRANTED AN EXTENSION |
| | TO HAVE ALL SEALS CHANGED OUT BY |
| | 12/31/2006 TO WORDING OF "LICENSE" IN |
| | SAID SEAL. |
| | |
| | 4) NOTE:PLEASE SEE THE FOLLOWING CODES |
| | SHALL BE REFLECTED ON PLANS. 2002 |
| | NFPA-70,2001 NFPA-101, 2002 NFPA-72, |
| | 1999 NFPA-20 |
| | |
| | |
| | 5) NOTE: PLEASE SUBMIT ALL |
| | SPECIFICATIONS / MANUFACTURES CUT SHEETS |
| | FOR FIRE PUMP, FIRE PUMP CONTROLLER. |
| | PLEASE CLARIFY TWO MEANS OF DISCONNECT |
| | AND OVER CURRENT PROTECTION? PLEASE SEE |
| | COMMENTARY IN THE NEC HANDBOOK UNDER |
| | 695.4 "TYPICALLY, THE SUPPLY CONDUCTORS |
| | OF THE POWER SOURCE ARE DIRECTLY |
| | CONNECTED, WITHOUT A DISCONNECTING MEANS |
| | OR OVERCURRENT PROTECTION, TO THE FIRE |
| | PUMP CONTROLLER OR COMBINATION FIRE PUMP |
| | CONTROLLER AND POWER TRANSFER SWITCH. |
| | HOWEVER, A SINGLE DISCONNECTING MEANS IS |
| | ALLOWED, PROVIDED ALL THE CONDITIONS IN |
| | 695.4(B), SUPERVISED CONNECTION, ARE |
| | MET". |
| | PLEASE KNOW, LOCKED ROTOR CURRENT FOR |
| | BOTH LOCATIONS ARE NOT THE NORM, AND THE |
| | FIRE PUMP CONTROLLER CONTAINS THE OCP, |
| | ATS, DISCONNECTING MEANS. |
| | 230.76.230.79, 6-3.2.2.1, 7-3.6 NFPA-20 |
| | PLEASE SEE FIRE PUMP MAIN LOCATION |
| | OUTSIDE WITH GENERAL ACCESS BY THE |
| | PUBLIC IS NOT PERMITTED PER NFPA-70 695, |
| | NFPA-20 CHAPTER 6,7 AND AHJ. |
| | PLEASE DETAIL ENCASEMENT OF FIRE PUMP |
| | SEC'S ETC NOT CONSIDERED OUTSIDE THE |
| | BLDG. 240.6 |
| | PLEASE INCLUDE ALL INFORMATION ON |
| | ELECTRICAL PLANS FOR FIRE PUMP AND |
| | LOCKED ROTOR. PLEASE INCLUDE HP RATING, |
| | SETTING FOR LOCKED ROTOR ETC |
| | 215.5 |
| | |
| | 6) NOTE: PLEASE PROVIDE THE GROUNDING |
| | ELECTRODE CONNECTIONS AND DETAILS. |
| | PLEASE SEE PLANS MENTIONS SEE NEC 250. |
| | THE CODE SHALL NOT BE "QUOTED" IN LIEU |
| | OF DETAIL OR SPECIFIC DESIGN. |
| | PLEASE SEE 250.50, 250.52, 250.104 ETC |
| | FOR ALL REQUIRED CONNECTION POINTS. |
| | PLEASE ALSO SEE "KEYED NOTES" #6 IS |
| | NOTED FOR GROUNDING ELECTRODE OF MAIN |
| | SERVICE, HOWEVER THIS NOTE DOES NOT |
| | CORRELATE WITH WHAT THE GEC SHOULD BE? |
| | |
| | 7) NOTE: PLEASE SEE PANEL "LD" IS |
| | REQUIRED TO CONTAIN AND MCB. NO |
| | EXCEPTIONS PER 230.70, 90.4 |
| | |
| | 8) NOTE: PLEASE SPECIFY THE PANEL LE AND |
| | LL AS CONTAINING "FEED-THRU" LUGS AS ONE |
| | PANEL BOARD MAY NOT CONTAIN OVER 42 OCP |
| | DEVICES. 408.15 |
| | |
| | 9) NOTE: PLEASE PLACE NOTE FOR ALL |
| | "SIGNAGE" WHICH WILL BE REQUIRED IN A |
| | MIN OF 1INCH LETTERING ON CONTRASTING |
| | BACKGROUND DENOTING ALL EQUIPMENT |
| | LOCATIONS. |
| | PLEASE SEE FIRE REVIEW NOTES AS LOCATION |
| | OF FACP MAY BE REQUIRED TO BE RELOCATED. |
| | PLEASE SEE THAT IN THE NEW LOCATION OF |
| | THE FACP WILL REQUIRE SIGNAGE AND |
| | MAPPING OF ALL SERVICE DISCONNECTING |
| | MEANS, FIRE PUMP, GENERATOR ETC. |
| | 215.5, 230.2, 700.8 ETC |
| | NFPA-20,-110 |
| | |
| | 10) NOTE: PLEASE SUBMIT SPECS/CUT SHEETS |
| | FOR GENERATOR. |
| | PLEASE COMPLETE PLANS FOR GENERATOR AS |
| | NO INFORMATION, RISER, ETC WAS |
| | SUBMITTED. |
| | PLEASE SEE COMMENTS UNDER OTHER BUILDING |
| | PERMITS FOR INFORMATION. |
| | |
| | 11) NOTE: PLEASE SEE NFPA-110 7.3.3* FOR |
| | MINIMUM LIGHTING LEVELS IN GENERATOR |
| | ROOM. (30 FT CANDLES. |
| | |
| | 12) NOTE: PLEASE CORRELATE FIXTURE |
| | SCHEDULE WITH ALL FIXTURES INDICATED ON |
| | PLANS. |
| | PLEASE SEE FIX H2, H2E, U-1, U-3,,, |
| | PLEASE SEE FIXTURES SHOWN ON PLANS, BUT |
| | NOT ON SCHEDULE. |
| | |
| | 13) NOTE: PLEASE PROVIDE COMPLETE PHOTO |
| | METRICS FOR STAIR TOWERS AND GARAGE |
| | AREAS PATHS FOR EGRESS. |
| | PLEASE SEE 2003 NFPA-101 7.8.1.3, |
| | 7.9.2.2 WHICH REQUIRES 10FT CANDLES (108 |
| | LUX) IN STAIR TOWERS UNDER NORMAL |
| | CONDITIONS AND 1 FT CANDLE UNDER |
| | EMERGENCY CONDITIONS. PLEASE SEE GARAGE |
| | AREAS REQUIRES 1FT CANDLE UNDER BOTH. |
| | THESE ARE AVERAGES, AND A TYPICAL DETAIL |
| | MAY BE PROVIDED FOR STAIRS AND EACH |
| | FLOOR. |
| | PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |
| | 14) NOTE: PLEASE PROVIDE ALL AREA AND |
| | ROOM DESIGNATIONS ON PLANS. |
| | 215.5 |
| | PLEASE SEE SOME AREAS WHERE THERE IS NOT |
| | INDICATION WHAT ROOMS ARE FOR. |
| | |
| | 15) NOTE: PLEASE SEE 230.2, 230.70, |
| | 230.72 FOR ALL MAINS AND ELECTRICAL |
| | SYSTEMS IN BUILDINGS. THIS IS ONE |
| | BUILDING AND SHALL CONTAIN ONLY ONE |
| | SERVICE. THE EMERGENCY SERVICE FOR THE |
| | FIRE PUMP IS PERMITTED UNDER THE |
| | EXCEPTIONS. |
| | |
| | 16) NOTE: PLEASE SEE 2004 FBC CHAPTER |
| | 13, 13-415.1.ABC.1.1 AND |
| | 13-415.1.ABC.1.2 FOR CONTROL OF |
| | LIGHTING. PLEASE KNOW, PARKING GARAGE |
| | AREAS, EGRESS AREAS WILL NOT BE |
| | CONSIDERED AS PART OF THESE |
| | REQUIREMENTS. |
| | PLEASE INDICATE CONTROL METHODS, TIME |
| | SCHEDULING ETC. |
| | PLEASE SEE 13-413.1ABC.1 FOR FEEDERS AND |
| | BRANCH CIRCUITS. PLEASE PROVIDE VOLTAGE |
| | DROP CALCULATIONS FOR WORST CASE |
| | SCENARIO AND/OR DIAGRAM FOR LONGEST |
| | RUN(S). PLEASE KNOW, THIS IS FOR THE |
| | RUNS AS NOTED ABOVE, NOT ALL AS MANY |
| | WILL NOT APPLY. |
| | PLEASE SEE ALL EXTERIOR LIGHTING SHALL |
| | BE CONTROL BY ONE OF THE METHODS AS |
| | LISTED IN 13-415.1.ABC.1.4 |
| | |
| | |
| | 17) NOTE: PLEASE SEE THAT ALL CONTINUOUS |
| | LOADS SHOULD BE INDICATED FOR FEEDERS |
| | ALSO. 215.3, 230.42 |
| | |
| | 18) NOTE: PLEASE INDICATE THE LOCATION |
| | OF THE GENERATOR ENUNCIATOR PANEL. |
| | |
| | 19) NOTE: PLEASE SEE ADDRESSING STOP. |
| | ONCE ADDRESS OF THE TWO GARAGES IS |
| | CONFIRMED ALL EMERGENCY NOTIFICATION |
| | SYSTEMS SHALL COMPLY PER FIRE REVIEW |
| | COMMENTS. PLEASE ALSO ADJUST PLANS, |
| | TITLE BLOCKS FOR ADDRESS AS "SAIL CLUB" |
| | NEEDS TO BE MORE SPECIFIC OF THE ACTUAL |
| | ADDRESS AND LOCATION. |
| | |
| | ** PLEASE BE AWARE OF COMMENTS FROM |
| | OTHER TRADES WHICH WILL HAVE AN AFFECT |
| | ON ELECTRICAL PLANS. |
| | |
| | ** WHEN RESUBMITTING THE PLANS, PLEASE |
| | BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO THREE COMPLETE SETS |
| | FOR EACH PERMIT. PLEASE SUBMIT ONE COPY |
| | OF THE OLD/VOIDED REMOVED SHEETS |
| | SEPARATELY FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW> IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |