2006-04-18 00:00:00BUILDING PLAN REVIEW
 PERMIT:06020120
 ADD:719 EXECUTIVE CTR DR ENCLOSED
 PARKING GARAGE
 CONT:PARKING BUILDERS, L.L.C.
 TEL: (918)252-7275
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 BUILDING PLAN REVIEW
 PERMIT:06020120
 ADD: 719 EXECUTIVE CENTER DR
 CONT: PARKING BUILDERS
 TEL: (918)252-7275
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)*******VERY IMPORTANT NOTE********
 WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3A)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING WILL REQUIRE A THRESHOLD
 INSPECTOR.FORMS WILL NEED TO BE FILED
 OUT FOR THE THRESHOLD INSPECTOR, CONTACT
 HAROLD PISKURA, INSPECTION SERVICES
 MANAGER @ (561)805-6711 TO SEET UP AN
 APPOINTMENT.
  
 3B) 109.3.6.1* THE ENFORCING AGENCY
 SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCINGAGENCY PRIOR
 TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD
 BUILDING.THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR
 THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTES.
  
 3D) NOTE: SINCE THIS BUILDING WILL BE A
 THRESHOLD STRUCTURE SUBMIT (3) OF ALL
 DOCUMENTS FOR REVIEW.
  
 3E) TWO PERMIT APPLICATIONS WERE
 SUBMITTED AND ONLY 3 SETS OF PLANS.
 NEITHER PERMIT APPLICATION INDICATES FOR
 WHICH BUILDING IT IS FOR, CAN'T ADDRESS
 THE PERMIT. 2ND WITH ONLY 3 SETS OF
 PLANS TO WHICH BUILDING WILL THEY BE
 APPLIED TOO?
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL LILI URSA FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. LILI URSA
 CONTACT NUMBER IS (561)822-1239.
  
 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
 7) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) SQ. FT. SPACE/ FL
 B) SQ. FT. FOOTPRINT
 C) SQ. FT. UNDER ROOF (TOTAL)FOR PARKING
  
 GARAGE INCLUDE ROOF
 D) OCCUPANT LOAD
 E ) FLOOD ZONE
 F) FLOOD ELEVATION
 G)L.O.M.R.
  
 8) GEOTECHNICAL REPORT THAT WORK WAS
 PREFORMED BY ARDAMAN NEEDS TO BE AN
 ORIGINAL WITH SIGNATURE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10)NOTE: 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11) PULL PLANS APART SO ONLY THE PAGES
 THAT DEAL WITH THE NORTH BUILDING ARE IN
 ONE SET AND THE PAGES THAT DEAL WITH THE
 SOUTH BUILDING ARE IN THE OTHER SET.
 REMEMBER 3SETS WILL BE REQUIRED FOR EACH
 BUILDING.
  
 12)SHEET A0.0 CODE REVIEW, TYPE IIA
 BUILDING IS LIMITED TO 5 STORIES. THE
 CODE REVIEW INFORMATION SHOULD ALSO
 INCLUDE FBC HEIGHT MODIFICATIONS FOUND
 IN 504.2 FOR AUTOMATIC SPRINKLER SYSTEM
 INCREASE.
  
 13) A1.1 & A1.7 GROUND FLOORS FOR BOTH
 BUILDINGS. THEREIS A DISCREPANCY
 BETWEEN THE PARKING GARAGE PLANS AND THE
 UPDATED LOFT PLANS DATED FEB. 10,06. TWO
 ADDITIONAL EGRESS DOORS WERE ADDED FROM
 THE CORRIDOR OF THE LOFTS THAT EMPTY
 INTO THE PARKING GARAGE. THESE DOORS ARE
 NOT REFLECTED IN THE CURRENT PARKING
 GARAGE PLANS.
  
 14) SHEET A1.1/ A1.3/ A1.7 & A1.8 ALL
 INDICATE VAN ACCESSIBLE PARKING SPACES
 BEING 8'-0" WIDE. A0.0 CODE REVIEW
 INDICATES USING FL ACCESSIBILITY CODE
 2004, WHEN USING THE FL ACCESSIBILITY
 CODE THE PARKING SPACES ARE 12'-0"
 WIDEW/5'-0" ACCESS AISLE, NOT 8'-0" WIDE
 PARKING SPACE, SEE FIGURE 9A, CHAPTER
 11, 2004 FBC. NOTE IF REVIEWED UNDER
 FAIR HOUSING GUIDELINE THE PARKING SPACE
 IS 8'-0" AND THE ACCESS AISLE FOR VANS
 REQUIRE AN ADDITIONAL 8'-0".
  
  
 15) SHEET A1.2 INDICATES (2) VAN
 ACCESSIBLE PARKING SPACES, INDICATE
 CLEARENCE CLEAR SPACE FROM FLOOR TO THE
 BOTTOM OF THE PRECAST BEAMS, A5.1
 INDICATES 11'-0" FROM TOP OF FLOOR TO
 TOP OF FLOOR. THE STRUCTURAL PLANS SCALE
 OUT TO BE 3'-6" WITH SLAB GIVING A CLEAR
 FLOOR TO BEAM BOTTOM OF 7'-6".
 11-4.6.5 VERTICAL CLEARENCE- AT PARKING
 SPACES COMPLYING WITH SECTION 11-4.1.2
 (5)(B), PROVIDE MINIMUM VERTICAL
 CLEARANCE OF 98 INCHES (2490 MM) AT THE
 PARKING SPACE AND ALONG AT LEAST ONE
 VEHICLE ACCESS ROUTE TO SUCH SPACES FROM
 SITE ENTRANCE(S) AND EXIT(S).
  
 16) ALL HANDICAPPED PARKING SPACES:
 11-4.6.2(1) ALL SPACES MUST BE LOCATED
 ON AN ACCESSIBLE ROUTE NO LESS THAN 44
 INCHES (1118 MM)WIDE SO THAT USERS WILL
 NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES.
  
 17A) PLANS DO NOT PROVIDE ANY SITE
 DETAILS LEADING FROM THE STAIR TOWERS?
 EXIT DISCHARGE . THAT PORTION OF A MEANS
 OF EGRESS SYSTEM BETWEEN THE TERMINATION
 OF AN EXIT AND A PUBLIC WAY.
 11-4.3.3 WIDTH.
 THE MINIMUM CLEAR WIDTH OF AN ACCESSIBLE
 ROUTE SHALL BE 36 INCHES (915 MM) EXCEPT
 AT DOORS (SEE SECTIONS 11-4.13.5 AND
 11-4.13.6 ). IF A PERSON IN A WHEELCHAIR
 MUST MAKE A TURN AROUND AN OBSTRUCTION,
 THE MINIMUM CLEAR WIDTH OF THE
 ACCESSIBLE ROUTE SHALL BE AS SHOWN IN
 FIGURE 11-7 (A) AND FIGURE 11-7 (B).
 EXCEPTION: CURB RAMPS THAT ARE A PART OF
 A REQUIRED MEANS OF EGRESS SHALL BE NOT
 LESS THAN 44 INCHES (1118 MM) WIDE.
  
 17B) A1.1 THERE IS NO DETAIL OR FLOOR
 SLAB ELEVATION GIVEN TO REPRESENT IF
 THERE IS A CHANGE IN GRADE WHERE THE
 PLAN INDICATES A DOUBLE LINE AROUND THE
 STAIR TOWERS, ENTRY INTO THE STRUCTURE,
 ETC? 11-4.3.3 CURB RAMPS THAT ARE A PART
 OF A REQUIRED MEANS OF EGRESS SHALL BE
 NOT LESS THAN 44 INCHES (1118 MM) WIDE.
  
 18) SHEET A1.1 VENT CHASE:
  
 18A) A1.1 SHAFT WALL TYPE "A" FOUND ON
 A6.1 NO WALL RATING OR U. L. LISTING FOR
 SHAFT WALL.707.4 FIRE-RESISTANCE RATING.
  
 SHAFT ENCLOSURES SHALL HAVE A FIRE
 RESISTANCE RATING OF NOT LESS THAN 2
 HOURS WHERE CONNECTING FOUR STORIES OR
 MORE AND NOT LESS THAN1 HOUR WHERE
 CONNECTING LESS THAN FOUR STORIES.
  
 18B) CUT SECTION THROUGH SHAFT AND TRASH
 ROOMSHEET A5.2 DETAIL (3) INDICATE
 THERE TO BE EXHAUST FANS SEE MEP PLANS ,
 NO MECHANICALPLANS SUBMITTED. SINCE THIS
 TRASH ROOM COMMUNICATES WITH THE SHAFT
 ( NO FIRE DAMPERS) THE ROOM WILL REQUIRE
 A 2 HR RATING WITH 1 1/2 HR RATED DOORS,
 NOT THE 3/4 HR IN SCHEDULE.
  
 18C) THE LOUVER BETWEEN THE GARAGE AND
 TRASHROOM WILL ALSO NEED TO HAVE FIRE
 DAMPERS.
  
 19)GARAGE- SHEET A1.1 CUT SECTION FOR
 THE WEST ELEVATION, SEE SPC8.02 DETAIL
 "H". INDICATES A SINGLE FOOTING FOR BOTH
 BUILDINGS THE LOFTS AND PARKING GARAGE.
 THIS WAS A COMMENT TO THE LOFT BUILDING
 ON THE FIRST ROUND OF COMMENTSTHAT THE
 2 BUILDINGS COULD NOT SHARE THE SAME
 FOUNDATION. NO GARENTEE THAT EITHER OR
 BOTH WILL BE BUILT THE SAME TIME. IF
 THIS HOLDS TRUE STRUCTURAL CRACKING MAY
 OCCUR SINCE THE DESIGN LOADS AND
 SETTLING WILL BE DIFFERENT THAN
 CALCULATED, CAUSING CRACKING AND OR IF
 THE OTHER BUILDING ISN'T BUILT ON THE
 SHARED FOOTER THERE WILL BE A DIFFERENCE
 IN THE WAY THE BUILDING WILL SETTLE.
 SEE LOFT BUILDING S-6 DATED 2-14-06
 FOR FOUNDATION DETAIL SHOULD BE NOTED ON
 BOTH SETS OF PLANS THE GARAGE FOOTER AND
 PRECAST WALL HAVE TO BE IN PLACE BEFORE
 THE LOFT FOUNDATION CAN BE STARTED.
  
 20) THE NEXT COMMENT DEALS WITH THE
 BUILDINGS HEIGHT. SEE DEFINITION:
 HEIGHT , BUILDING. THE VERTICAL DISTANCE
 FROM GRADE PLANE TO THE AVERAGE HEIGHT
 OF THE HIGHEST ROOF SURFACE.
  
 GRADE PLANE. A REFERENCE PLANE
 REPRESENTING THE AVERAGE OF FINISHED
 GROUND LEVEL ADJOINING THE BUILDING AT
 EXTERIOR WALLS. WHERE THE FINISHED
 GROUND LEVEL SLOPES AWAY FROM THE
 EXTERIOR WALLS, THE REFERENCE PLANE
 SHALL BE ESTABLISHED BY THE LOWEST
 POINTS WITHIN THE AREA BETWEEN THE
 BUILDING AND THE LOT LINE OR, WHERE THE
 LOT LINE IS MORE THAN 6 FEET (1829 MM)
 FROM THE BUILDING, BETWEEN THE BUILDING
 AND A POINT 6 FEET (1829 MM) FROM THE
 BUILDING.
  
 SHEET A2.1 INIDCATES A 2'-0" DIFFERENCE
 IN GRADE, SAID PLAN ALSO INDICATES A
 ROOF HEIGHT OF 74'-0" ALTHOUGH A1.6 ALSO
 SHOWS A 78.49' ROOF HEIGHT.
  
 THE ISSUE IS WHAT IS THE TRUE HEIGHT OF
 THE BUILDING. THE FIRE DEPARTMENT TO
 FIGHT A FIRE HAS CLEAR ACCESS ONLY ON
 ONE SIDE. TO DETERMINE THE AVERAGE GRADE
 PLANE THIS ELEVATION SHALL BE TAKEN
 6'-0" OUTSIDE OF THE LOFT UNITS. PLEASE
 PROVIDE SITE PLAN WITH CALCULATIONS FOR
 GRADE.
  
 THE SECOND ISSUE WILL BE FOR THE
 DESIGNER TO ALSO FIGURE THE AVERAGE
 HEIGHT OF HIGHEST ROOF SURFACE. PROVIDE
 CALCULATIONS.
  
 THE RESULTS OF THIS EXERCISE PLUS THE
 ADDITIONAL HEIGHT REQUIREMENT FROM
 COMMENT (15) MAY PUT THIS BUILDING INTO
 THE REQUIREMENTS FOR HIGHRISE SECTION
 403 OF 2004 FBC.
  
 21)A1.1 DOOR N103 FPL VAULT INDICATES
 USE OF 3HR RATED DOOR FRAME WITH 45MIN
 LOUVERED DOORS?
  
 22) SHEET A1.1A INDICATES ADETENTION
 POND, THE WALL CLOSEET TO THE BOTTOM OF
 THE PAGE THE WEST WALL INDICATES A WALL
 OPENING, THIS IS A FIRE WALL, PLEASE
 EXPLAIN RATIONALE?
  
 23) SHEET A1.3 PLANS INDICATE A DOOR
 IN EACH FIRE WALL. THE DOORS ARE NOT
 GIVEN ANY DESIGNATION OR MARKING AND CAN
 NOT CONCLUDE FIRE RATING OF DOORS AND
 FRAMES.
 705.6.1 STEPPED BUILDINGS .
 WHERE A FIRE WALL SERVES AS AN EXTERIOR
 WALL FOR A BUILDING AND SEPARATES
 BUILDINGS HAVING DIFFERENT ROOF LEVELS,
 SUCH WALL SHALL TERMINATE AT A POINT NOT
 LESS THAN 30 INCHES (762 MM) ABOVE THE
 LOWER ROOF LEVEL, PROVIDED THE EXTERIOR
 WALL FOR A HEIGHT OF 15 FEET (4572 MM)
 ABOVE THE LOWER ROOF IS NOT LESS THAN
 1-HOUR FIRE-RESISTANCE-RATED
 CONSTRUCTION FROM BOTH SIDES WITH
 OPENINGS PROTECTED BY ASSEMBLIES HAVING
 A ?-HOUR FIRE PROTECTION RATING.
  
 24A) SHEET A1.3 ELEVATED WALKWAYS NOT
 PART OF THIS PERMIT, BUT NOTE # 3 DOORS
 BY OTHERS, WILL A SEPERATE PERMIT BE
 TAKEN OUT FOR THESE DOORS AS WELL?
  
 24B) WITH BUILDINGS BEING PHASED AND
 C.O.'S BEING ISSUED AT DIDDERENT TIMES
 HOW WILL THIS OPENING BE SEALED OFF IF
 THE ELEVATED WALKWAY HASN'T BEEN BUILT
 AND ITS TIME TO C.O. THE PARKING GARAGE.
  
 24C) THIS SAME DOOR WILL REQUIRE A 1 1/2
 HR PROTECTIVE (706.7) SEE FIGURE3104.5
 PEDESTRIAN WALKWAY BUILDING INTERFACE.
  
 24D) NOTE (NOT PART OF THIS PERMIT)
 ELEVATED COVERED PEDESTRIAN
 WALKWAYS, SEE 3104.9 FOR EXIT ACCESS
 TRAVEL.
  
 25) A1.5 STAIRWELLS, 1022.3 OPEN SIDE.
 EXTERIOR EXIT RAMPS AND STAIRWAYS
 SERVING AS AN ELEMENT OF A REQUIRED
 MEANS OF EGRESS SHALL BE NOT LESS THAN
 50 PERCENT OPE N ON ONE SIDE. OUTSIDE
 STAIRS SHALL BE ARRANGED TO RESTRICT THE
 ACCUMULATION OF SMOKE. SEE CODE
 COMMENTARY TO BE CONSIDERED OPEN STAIRS,
 THE OPENINGS ON EACH AND EVERY FLOOR AND
 LANDING MUST TOTAL 50% GREATER ON ONE
 SIDE.
  
 26) SHEET A5.4 DETAILS REFER BACK TO
 STRUCTURAL SHEETS FOR STEEL FRAMING
 SECTION 9 & 12.
  
 27) SHEET A5.4 SAME DETAILS INDICATE USE
 OF 5/8" PLYWOOD DECKING. TABLE 601 NOTE
 (2)(II) ALLOWS FRTW FIRE RETARDANT
 TREATED WOOD TO BE USED AS PART OF THE
 ROOF CONSTRUCTION SYSTEM.
  
 28) PLANS INDICATE USE OF AWNINGS ON
 THE EXTERIOR OF THE BUILDING IN THE OPEN
 POSITION.PROVIDE AN ENGINEERS REPORT
 FOR THIS TYPE OF APPLICATION ,
 INDICATING THESE ARE TO BE CONSIDERED IN
 THE OPEN POSITION IN A HIGH WIND EVENT.
 PROVIDE ALSO THE ANCHORING REQUIRED FOR
 KEEPING THE AWNINGS FROM BECOMING
 DETATCHED FROM THE BUILDING.
  
 29) A5.4 DETAIL DETAIL# 9 PROVIDE
 COMPLIANCE WITH ATTACHMENT OF 2X4 FOR
 RIDGE AND HIP TILE, SHOW COMPLIANCE WITH
  
 1507.3.8 FRSA/RTI 0730/08-05 TABLE 11
 FOR 140 MPH.
  
 30) SHEET A5.4VAARIOUS DETAILS
 INDICATE FOAM ON THE EXTERIOR OF
 BUILDING AS TRIM.1406.2.2
 ARCHITECTURAL TRIM .
 IN BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION THAT DO NOT EXCEED THREE
 STORIES OR 40 FEET (12 192 MM) IN HEIGHT
 ABOVE GRADE PLANE, EXTERIOR WALL
 COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF WOOD WHERE PERMITTED BY
 SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE
 EXTERIOR WALL COVERINGS, OTHER THAN
 FIRE-RETARDANT-TREATED WOOD COMPLYING
 WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10
 PERCENT OF AN EXTERIOR WALL SURFACE AREA
 WHERE THE FIRE SEPARATION DISTANCE IS 5
 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE SHALL BE
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE
 MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED
 NONCOMBUSTIBLE BRACKETS.
  
 31) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 32)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR DOORS HOLLOW STEEL
 B) EXTERIOR DOORS LOUVER STEEL
 C) TRUSS ANCHORS
 D) ROOFING ASSEMBLIES
 E) LOUVERS
  
 33) ADDITION TO COMMENT# 27, ENGINEER
 WILL NEED TO PROVIDEFRTW PLYWOOD
 ATTACHMENT TO METAL TRUSS ASSEMBLY.
 ZONES 1,2,3.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
 34)