Plan Review Notes
Plan Review Notes For Permit 06020087
Permit Number 06020087
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-09 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE THE MAINS DISCONNECT
 "A" MAY NOT BE USED AS A RACEWAY FOR
 SEC'S TO MAIN "B". PLEASE SEE 230.7
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS
 SHALL NOT BE INSTALLED IN THE SAME
 SERVICE RACEWAY OR SERVICE CABLE.
 ALL FEEDER AND BRANCH-CIRCUIT CONDUCTORS
 MUST BE SEPARATED FROM SERVICE
 CONDUCTORS.
  
 2))NOTE: PLEASE SEE THE "GAS POOL
 HEATER" IS BEING SHOWN WITH AN
 ELECTRICAL LOAD AND CALCULATIONS
 INDICATING THIS HEATER AND AN ELECTRICAL
 TYPE HEATER/HEAT PUMP?
 PLEASE CLARIFY WHICH.
  
 3)NOTE: PLEASE SHOW SERVICE ON PLANS, AS
 PLANS ONLY INDICATE A METER ON THE
 OUTSIDE OF THE HOUSE. MAIN(S)?
 215.5
  
 4)NOTE: PLEASE SEE 210.8A7 WHICH
 REQUIRES ALL RECEPTS WITHIN 6' OF A WET
 BAR TO BE GFI.
 PLEASE SEE REDLINED PLANS.
  
 5 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE SEE THIS IS SHOWN AS PART OF THE
 GEN LT LOADS FOR LTS AND RECEPTS. THIS
 SHOULD BE ADDED TO GEN LIGHTING LOAD.
  
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONLY ONE COPY OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REVIEW.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 PLEASE ALSO CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THAT OF THE
 FIXTURES ON PANEL SCHEDULE.