| 2006-02-09 00:00:00 | ********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE THE MAINS DISCONNECT |
| | "A" MAY NOT BE USED AS A RACEWAY FOR |
| | SEC'S TO MAIN "B". PLEASE SEE 230.7 |
| | CONDUCTORS OTHER THAN SERVICE CONDUCTORS |
| | SHALL NOT BE INSTALLED IN THE SAME |
| | SERVICE RACEWAY OR SERVICE CABLE. |
| | ALL FEEDER AND BRANCH-CIRCUIT CONDUCTORS |
| | MUST BE SEPARATED FROM SERVICE |
| | CONDUCTORS. |
| | |
| | 2))NOTE: PLEASE SEE THE "GAS POOL |
| | HEATER" IS BEING SHOWN WITH AN |
| | ELECTRICAL LOAD AND CALCULATIONS |
| | INDICATING THIS HEATER AND AN ELECTRICAL |
| | TYPE HEATER/HEAT PUMP? |
| | PLEASE CLARIFY WHICH. |
| | |
| | 3)NOTE: PLEASE SHOW SERVICE ON PLANS, AS |
| | PLANS ONLY INDICATE A METER ON THE |
| | OUTSIDE OF THE HOUSE. MAIN(S)? |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE 210.8A7 WHICH |
| | REQUIRES ALL RECEPTS WITHIN 6' OF A WET |
| | BAR TO BE GFI. |
| | PLEASE SEE REDLINED PLANS. |
| | |
| | 5 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE SEE THIS IS SHOWN AS PART OF THE |
| | GEN LT LOADS FOR LTS AND RECEPTS. THIS |
| | SHOULD BE ADDED TO GEN LIGHTING LOAD. |
| | |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONLY ONE COPY OF OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REVIEW. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | PLEASE ALSO CORRELATE THE NUMBER OF |
| | RECESSED LTS ON PLANS WITH THAT OF THE |
| | FIXTURES ON PANEL SCHEDULE. |