Plan Review Notes
Plan Review Notes For Permit 06020077
Permit Number 06020077
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:00DENIED
  
 1) THE FLORIDA PRODUCT APPROVAL
 COVERSHEET IS FOR BUILT UP ROOFS, NOT
 FOR THE RUBEROID MODIFIED BITUMEN SYSTEM
 LISTED IN THE NOA THAT WAS SUBMITTED.
 SEE FL 617-R1.
  
 2) THE ASSEMBLY THAT IS PROPOSED AND
 LISTED ON PAGES 11 AND 12 OF THE NOA HAS
 A MAXIMUM DESIGN PRESSURE OF -45 PSF
 WHICH WILL NOT MEET REQUIRED UPLIFT
 PRESSURS ON THE STRUCTURE. LIMITATION #9
 FROM THE NOA DOES NOT ALLOW FOR ENHANCED
 FASTENING FOR THIS ASSEMBLY.
  
 3) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE ON THE APPLICATION. THIS
 REVIEW IS BASED ON A MEAN ROOF HEIGHT OF
 LESS THAN 30 FEET.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  