| Plan Review Notes For Permit 06020067 |
| Permit Number |
06020067 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-13 00:00:00 | DENIED; | | | 1.WATER HEATER PAN DRAIN IS NOT SHOWN ON | | | PAGE P-2.1 AS NOTED ON WATER HEATER | | | DETAIL. MECHANICAL ROOM IS SHOWN ON PAGE | | | P-2.2. AND NO SANITARYDRAINAGE IS | | | SHOWN. A FLOOR DRAIN SHOULD NOT BE USED | | | IN A MECHANICAL ROOM BECAUSE THE TRAP | | | WOULD BE SUBJECT TO A PNEUMATIC PRESSURE | | | DIFFERENTIAL OF MORE THAN ONE INCH OF | | | WATER COLUMN. FBC-2004 PLUMBING SEC. | | | 901.2. | | | 2.PAGE P-5.1 SANITARY AND WATER RISER | | | DIAGRAMS SHOW A MOP SINK. PAGE P-2.1, | | | SANITARY FLAT DRAWING, SANITARY PIPING | | | NOT SHOWN. PAGE P-3.2 WATER PIPING NOT | | | SHOWN TO MOP SINK. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|