2006-03-13 00:00:00DENIED;
 1.WATER HEATER PAN DRAIN IS NOT SHOWN ON
 PAGE P-2.1 AS NOTED ON WATER HEATER
 DETAIL. MECHANICAL ROOM IS SHOWN ON PAGE
 P-2.2. AND NO SANITARYDRAINAGE IS
 SHOWN. A FLOOR DRAIN SHOULD NOT BE USED
 IN A MECHANICAL ROOM BECAUSE THE TRAP
 WOULD BE SUBJECT TO A PNEUMATIC PRESSURE
 DIFFERENTIAL OF MORE THAN ONE INCH OF
 WATER COLUMN. FBC-2004 PLUMBING SEC.
 901.2.
 2.PAGE P-5.1 SANITARY AND WATER RISER
 DIAGRAMS SHOW A MOP SINK. PAGE P-2.1,
 SANITARY FLAT DRAWING, SANITARY PIPING
 NOT SHOWN. PAGE P-3.2 WATER PIPING NOT
 SHOWN TO MOP SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695