Plan Review Notes
Plan Review Notes For Permit 06020067
Permit Number 06020067
Review Stop M
Sequence Number 2
Notes
Date Text
2006-03-14 00:00:00*** DENIED ***
 1) AS STATED IN LAST REVIEW 02-13-06 #3.
 FIRE DAMPERS ARE REQUIRED WHERE DUCTS
 ARE PENETRATEING THE FIRE RATED WALLS TO
 COURT ROOMS (847 & 838) PER 2004 FBC
 716.5.1 . PLEASE SEE TRANSFER RETURN AIR
 DUCT FROM COURTROOM 847 TO ROOM 873;
 RETURN AIR DUCT FROM COURTROOM 847 TO
 ROOM 845; TRANSFER RETURN AIR DUCT FROM
 COURTROOM 838 TO ROOM 872; AND RETURN
 AIR DUCT FROM COURTROOM 838 TO ROOM 836.
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.