| Plan Review Notes For Permit 06020067 |
| Permit Number |
06020067 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-14 00:00:00 | *** DENIED *** | | | 1) AS STATED IN LAST REVIEW 02-13-06 #3. | | | FIRE DAMPERS ARE REQUIRED WHERE DUCTS | | | ARE PENETRATEING THE FIRE RATED WALLS TO | | | COURT ROOMS (847 & 838) PER 2004 FBC | | | 716.5.1 . PLEASE SEE TRANSFER RETURN AIR | | | DUCT FROM COURTROOM 847 TO ROOM 873; | | | RETURN AIR DUCT FROM COURTROOM 847 TO | | | ROOM 845; TRANSFER RETURN AIR DUCT FROM | | | COURTROOM 838 TO ROOM 872; AND RETURN | | | AIR DUCT FROM COURTROOM 838 TO ROOM 836. | | | PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|