Plan Review Notes
Plan Review Notes For Permit 06020067
Permit Number 06020067
Review Stop P
Sequence Number 1
Notes
Date Text
2006-02-11 00:00:00 
 PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC 2004 BUILDING CH 11
 DENIED
 1)SHT 8.10 DETAIL (E)
 BREAK ROOMS #863,815,827.
 BASE CABINET DOORS UNDER SINKS.
 SINKS
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
  
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM)
 WIDE, AND 19 INCHES (485 MM) DEEP SHALL
 BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6?
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
  
 2)PRIVATE TOILET ROOM #818
 SECTION 11-4.1.3
 11) TOILET FACILITIES. IF TOILET ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH
 SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF
 SPECIFIC SPACES (I.E., A PRIVATE TOILET
 ROOM FOR THE OCCUPANT OF A PRIVATE
 OFFICE) SHALL BE ADAPTABLE. IF BATHING
 ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE BATHROOM SHALL COMPLY WITH
 SECTION 11-4.23. ACCESSIBLE TOILET ROOMS
 AND BATHING FACILITIES SHALL BE ON AN
 ACCESSIBLE ROUTE.
 11-4.22.2 DOORS.
 (1) ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH SECTION 11-4.13. DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
  
 3) SHT P-01 WATER HEATER DETAIL
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 607.3.1 PRESSURE-REDUCING VALVE.
 FOR WATER SERVICE SYSTEM SIZES UP TO AND
 INCLUDING 2 INCHES (51 MM), A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED
 WHERE, BECAUSE OF THERMAL EXPANSION, THE
 PRESSURE ON THE DOWNSTREAM SIDE OF A
 PRESSURE-REDUCING VALVE EXCEEDS THE
 PRESSURE-REDUCING VALVE SETTING.
  
 4)SHT-5.1 DOMESTIC WATER ISOMETRIC
 AIR CHAMBERS NOT APPROVED
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED
 TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010.
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  