| Plan Review Notes For Permit 06020067 |
| Permit Number |
06020067 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-14 00:00:00 | DENIED: | | | | | | 1) SHALL COMPLY WITH NFPA 101 LIFE | | | SAFETY CODE 2003 EDITION AND NFPA 1 | | | UNIFORM FIRE CODE 2003 EDITION. | | | | | | 2) CORRIDOR # 813 APPEARS TO EXCEED 50 | | | FEET TRAVEL DISTANCE FOR DEAD-END | | | CORRIDORS CHAPTER 38.2.5.2.1, NFPA 101. | | | | | | 3) FIRE ALARM NOTE # 17 HVAC DUCT SMOKE | | | DETECTORS SHALL BE CONNECTED TO THE FIRE | | | ALARM CONTROL PANEL AND SHALL INITIATE A | | | GENERAL FIRE ALARM SIGNAL, NOT A | | | SUPERVISORY SIGNAL. | | | | | | 4) DELAYED-EGRESS LOCKS SHALL COMPLY | | | WITH NFPA 101 CHAPTER 7.2.1.6.1, AND | | | ACCESS-CONTROLLED EGRESS DOORS SHALL | | | COMPLY WITH NFPA 101 CHAPTER 7.2.1.6.2. | | | | | | 5) SEPARATE SHOP DRAWING AND PERMIT | | | APPLICATION ARE REQUIRED FOR FIRE ALARM | | | SYSTEM REMODEL. | | | | | | 6) SEPARATE SHOP DRAWING AND PERMIT | | | APPLICATION ARE REQUIRED FOR FIRE | | | SPRINKLER SYSTEM REMODEL. | | | | | | 7) INTERIOR WALL AND CEILING FINISH | | | MATERIAL COMPLYING WITH NFPA 101 SECTION | | | 10.2 SHALL CLASS A OR CLASS B IN EXITS | | | AND IN EXIT ACCESS CORRIDORS. | | | | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|