Plan Review Notes
Plan Review Notes For Permit 06020067
Permit Number 06020067
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-02-14 00:00:00DENIED:
  
 1) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE 2003 EDITION AND NFPA 1
 UNIFORM FIRE CODE 2003 EDITION.
  
 2) CORRIDOR # 813 APPEARS TO EXCEED 50
 FEET TRAVEL DISTANCE FOR DEAD-END
 CORRIDORS CHAPTER 38.2.5.2.1, NFPA 101.
  
 3) FIRE ALARM NOTE # 17 HVAC DUCT SMOKE
 DETECTORS SHALL BE CONNECTED TO THE FIRE
 ALARM CONTROL PANEL AND SHALL INITIATE A
 GENERAL FIRE ALARM SIGNAL, NOT A
 SUPERVISORY SIGNAL.
  
 4) DELAYED-EGRESS LOCKS SHALL COMPLY
 WITH NFPA 101 CHAPTER 7.2.1.6.1, AND
 ACCESS-CONTROLLED EGRESS DOORS SHALL
 COMPLY WITH NFPA 101 CHAPTER 7.2.1.6.2.
  
 5) SEPARATE SHOP DRAWING AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE ALARM
 SYSTEM REMODEL.
  
 6) SEPARATE SHOP DRAWING AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 7) INTERIOR WALL AND CEILING FINISH
 MATERIAL COMPLYING WITH NFPA 101 SECTION
 10.2 SHALL CLASS A OR CLASS B IN EXITS
 AND IN EXIT ACCESS CORRIDORS.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL