Plan Review Notes For Permit 06020067
Permit Number 06020067
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-24 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE REFERENCE ALL CURRENT
 CODE IN EFFECT FOR PLANS AND DESIGN.
 PLEASE SEE LOCATIONS ON PLANS WHICH
 REFLECT THE 2001 FBC ETC.
 ** PLEASE REFERENCE THE FOLLOWING:
 2003 NFPA-101, 2002 NFPA-72, 2002
 NFPA-70, AND 2004 FBC.
  
 2)NOTE: PLEASE SEE NEC 645 AND NFPA-75
 FOR ALL THE REQUIREMENTS WHICH WILL NEED
 TO BE ADJUSTED ON PLANS.
 PLEASE SEE 645.5,645.7,645.10 ETC
 PLEASE ADJUST LOADS FOR EQUIPMENT.645.5
 ** PLEASE SEE OTHER REVIEWS AND PLEASE
 BE SURE TO ADJUST MECH, AND BLDG PLANS
 ACCORDINGLY.
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42 ETC
  
 4)NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE CONNECTION FOR TRANSFORMER,
 PER 250.30 AND 250.58
  
 5)NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN NEW 400A MIAN
 AND MDP-1.
 250.110,250.122
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT PER 110.9,
 215.5
 ** IT IS NOTED THESE ARE SHOWN FOR
 PANELS,HOWEVER PLEASE PROVIDE FOR NEW
 MAIN DISCONNECT.
  
 7)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM LTS WHICH REQUIRES THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 ** PLEASE KNOW, IF THESE THE LIGHTING IN
 THE ARE OF FLOOR GOES OUT, NO MEANS OF
 EGRESS LIGHTING WOULD BE PROVIDED AS THE
 EM WOULD NOT COME ON UNLESS BLDG
 ELECTRICAL UTILITY SERVICES FAILS. THIS
 WOULD LEAVE ANY ONE AREA /FLOOR IN TOTAL
 DARKNESS. PLEASE EITHER ADD ADDTIONAL
 BATTERY BACK UP FIXTURES TO AREA FOR
 EGRESS, PLACE FIXTURES SHOWN ON LOCAL
 CIRCUITS.
 700.12,NFPA-101,7.8,7.9.2.2
  
 8)NOTE: PLEASE SEE 2004 FBC CHAPTER 13
 FOR COMMERCIAL BLDGS AND THE ENERGY CODE
 FOR PLANS AND DESIGS. IT IS NOTED, SOME
 MD/ ARE NOTED, HOWEVER PLEASE PROVIDE AL
 INFORMATION AS FOLLOWS AND COMPLETE
 PLANS FOR LAYOUTS, SCHEDULING,VOLTAGE
 DROPS, OVER-RIDES, SPACE
 CONTROLS,CALCULATIONS ETC.
 PLEASE SEE :
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2,
 13-413.1.ABC.1.1 & .1.2, 13-415.1.ABC.1,
  
 &.1.1
 PLEASE SEE ALL DESIGNS SHALL MEET 2004
 FBC.
 PLEASE ALSO SEE COMPLETION DOC'S
 REQUIRED 13-413.1.ABC.2.1.&.2
 ** PLEASE KNOW, SPEC SHEETS ON DEVICES,
 AND SYSTEM BEING INSTALLED WILL BE
 REQUIRED TO BE SUBMITTED, PLEASE PROVIDE
 A MIN OF TWO COPIES.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  