| 2006-02-24 00:00:00 | ******** UNSAT ********* |
| | |
| | 1)NOTE: PLEASE REFERENCE ALL CURRENT |
| | CODE IN EFFECT FOR PLANS AND DESIGN. |
| | PLEASE SEE LOCATIONS ON PLANS WHICH |
| | REFLECT THE 2001 FBC ETC. |
| | ** PLEASE REFERENCE THE FOLLOWING: |
| | 2003 NFPA-101, 2002 NFPA-72, 2002 |
| | NFPA-70, AND 2004 FBC. |
| | |
| | 2)NOTE: PLEASE SEE NEC 645 AND NFPA-75 |
| | FOR ALL THE REQUIREMENTS WHICH WILL NEED |
| | TO BE ADJUSTED ON PLANS. |
| | PLEASE SEE 645.5,645.7,645.10 ETC |
| | PLEASE ADJUST LOADS FOR EQUIPMENT.645.5 |
| | ** PLEASE SEE OTHER REVIEWS AND PLEASE |
| | BE SURE TO ADJUST MECH, AND BLDG PLANS |
| | ACCORDINGLY. |
| | |
| | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 215.3,230.42 ETC |
| | |
| | 4)NOTE: PLEASE PROVIDE GROUNDING |
| | ELECTRODE CONNECTION FOR TRANSFORMER, |
| | PER 250.30 AND 250.58 |
| | |
| | 5)NOTE: PLEASE CLARIFY EQUIPMENT |
| | GROUNDING METHOD BETWEEN NEW 400A MIAN |
| | AND MDP-1. |
| | 250.110,250.122 |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT PER 110.9, |
| | 215.5 |
| | ** IT IS NOTED THESE ARE SHOWN FOR |
| | PANELS,HOWEVER PLEASE PROVIDE FOR NEW |
| | MAIN DISCONNECT. |
| | |
| | 7)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM LTS WHICH REQUIRES THE |
| | BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | ** PLEASE KNOW, IF THESE THE LIGHTING IN |
| | THE ARE OF FLOOR GOES OUT, NO MEANS OF |
| | EGRESS LIGHTING WOULD BE PROVIDED AS THE |
| | EM WOULD NOT COME ON UNLESS BLDG |
| | ELECTRICAL UTILITY SERVICES FAILS. THIS |
| | WOULD LEAVE ANY ONE AREA /FLOOR IN TOTAL |
| | DARKNESS. PLEASE EITHER ADD ADDTIONAL |
| | BATTERY BACK UP FIXTURES TO AREA FOR |
| | EGRESS, PLACE FIXTURES SHOWN ON LOCAL |
| | CIRCUITS. |
| | 700.12,NFPA-101,7.8,7.9.2.2 |
| | |
| | 8)NOTE: PLEASE SEE 2004 FBC CHAPTER 13 |
| | FOR COMMERCIAL BLDGS AND THE ENERGY CODE |
| | FOR PLANS AND DESIGS. IT IS NOTED, SOME |
| | MD/ ARE NOTED, HOWEVER PLEASE PROVIDE AL |
| | INFORMATION AS FOLLOWS AND COMPLETE |
| | PLANS FOR LAYOUTS, SCHEDULING,VOLTAGE |
| | DROPS, OVER-RIDES, SPACE |
| | CONTROLS,CALCULATIONS ETC. |
| | PLEASE SEE : |
| | 13-415.1.ABC.1.1, 13-415.1.ABC.1.2, |
| | 13-413.1.ABC.1.1 & .1.2, 13-415.1.ABC.1, |
| | |
| | &.1.1 |
| | PLEASE SEE ALL DESIGNS SHALL MEET 2004 |
| | FBC. |
| | PLEASE ALSO SEE COMPLETION DOC'S |
| | REQUIRED 13-413.1.ABC.2.1.&.2 |
| | ** PLEASE KNOW, SPEC SHEETS ON DEVICES, |
| | AND SYSTEM BEING INSTALLED WILL BE |
| | REQUIRED TO BE SUBMITTED, PLEASE PROVIDE |
| | A MIN OF TWO COPIES. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |