2006-02-24 00:00:00 
  
 DENIED
  
 1) PERMIT VALUE IS LOW AND WILL BE
 ADJUSTED TO REFLECT THE MARSHALL AND
 SWIFT CONSTRUCTION COSTS GUIDE AND
 THEREFORE WILL INCREASE THE PERMIT FEE
  
 2) THE SINGLE HUNG PRODUCT THAT IS
 CHOSEN DOES NOT MEET THE EMERGENCY
 EGRESS REQUIREMENTS FOR THE BEDROOMS
 PER R310.1.1 THROUGH R310.1.4 FBC
  
 3) STATE ON DRAWING THAT NO ALTERATION
 TO OPENINGS IS REQUIRED AND HOW MANY
 STORIES THE BUILDING HAS. IF ALTERATIONS
 NEED TO BE MADE DETAIL DRAWINGS WILL BE
 REQUIRED
  
 4) IF WINDOWS ARE NON-IMPACT THE CORRECT
 PRODUCT APPROVALS SHALL BE PROVIDED AND
 IMPACT PROTECTION WILL BE REQUIRED
  
  
 BLDG PLAN REVIEW