| 2006-03-22 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 2) THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| | COST EXCLUDING LAND VALUE. OUR VALUATION |
| | REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| | AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3 FBC* |
| | |
| | 3) PLANS WERE SUBMITTED AFTER JAN.1, |
| | 2004 AND AS SUCH THE ENGINEER'S SEAL |
| | WAS MANDATED TO CHANGE IN APPEARANCE PER |
| | 61G15-23.001 FAC |
| | |
| | 4) PROVIDE DRAWING OF EXISTING LAYOUT |
| | WITH AJOINING ROOMS FOR BETTER |
| | UNDERSTANDING OF ADDITION OR MOVING OF |
| | EXISTING STRUCTURE AND SYSTEMS SUCH AS |
| | PLUMBING, MECHANICAL AND ELEC. |
| | |
| | 5) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | CONFORM WITH R802.10.1 FBC |
| | |
| | 6) DRAWING S/1 SPECIFIES REMOVAL OF WALL |
| | BELOW TIE BEAM, DOES PARALLAM BEAM |
| | REPLACE TIE BEAM? PLEASE CLARIFY |
| | |
| | 7) DRAWING S/3 DETAIL 1 SHOWS TRUSS |
| | TAILS, WILL THEY BE REMOVED? ALSO IS |
| | TRIPLE JACK POST TO RUN ALLTHE WAY TO |
| | PARALLAM BEAM FOR BEARING WITHOUT DOUBLE |
| | TOP PLATE BECAUSE THERE IS NO WALL |
| | UNDERNEATH. CLARIFY ON DRAWINGS |
| | |
| | 8) DRAWING S/2 SHOWS AN EXISTING BEAM TO |
| | REMAIN, IF BEAM IS IN CEILING WHAT IS |
| | RELATIONSHIP TO NEW TRUSS GIRDER AND |
| | ATTACHMENT TO NEW PARALLAM BEAM? |
| | |
| | 9) ELEVATION DRAWING SHALL PROVIDE |
| | FIN.FL. EL, BEAM EL, AND MEAN ROOF HT. |
| | |
| | 10) SUBMIT SOIL REPORT, MAY USE COPY OF |
| | EXISTING PER |
| | |
| | 11) SUBMIT A SOIL REPORT PER 1802.1- |
| | 1802.2.2 FBC |
| | |
| | 12) THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | |
| | IS RELEVANT. THESE SHOULD INCLUDE THE |
| | FLORIDA STATE APPROVAL COVER PAGES, AND |
| | THE PRODUCT NOA THAT LISTS THE SYSTEM |
| | COMPONENTS/ FASTENER LIST PAGES, THE |
| | PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM |
| | TO BE USED AND THE GENERAL LIMITATIONS |
| | PAGE. ALL CAN BE FOUND ON |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 13) PLEASE SEE JELD-WEN DOORS (THE FIRST |
| | 4 PAGES IS THE STATE APPROVAL COVER |
| | SHEETS). THESE ARE REQUIRED FOR THE |
| | SHINGLES ALONG WITH THE UPDATED NOA, THE |
| | STORM PANELS AND WINDOWS ARE OK AS IS |
| | |
| | 14) PROVIDE PRODUCT APPROVAL FOR FLAT |
| | AREA OF THE ROOF AS SHINGLES ARE NOT |
| | PERMITTED ON ROOF SLOPES LESS THAN 2/12 |
| | |
| | 15) THOSE PRODUCTS WHICH ARE REGULATED |
| | BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 WPB |
| | AMENDMENTS TO FBC 2004 |
| | |
| | 16) STRUCTURAL NOTES ON S/3 UPDATE NOTES |
| | TO 2004. WIND LOADS ARE NOW 1609 |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH |
| | ADMINISTATIVE AMMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |