| 2006-06-20 00:00:00 | ********* UNSAT 4TH REVIEW ********** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS |
| | REVIEWS DATED 3/6/06,5/09/06 6/11/06 |
| | |
| | 1) NOTE: PLEASE SEE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1,.1.2, .1.3 ETC |
| | 13-415.1.ABC.3, 13-415.1.AB.1 , |
| | 13-415.2.ABC.1 ETC. |
| | PLEASE SEE MISSING ENERGY CODE |
| | COMPLIANCE FORMS (FORM C) 2004, SEE |
| | ABOVE. |
| | |
| | |
| | PLEASE SEE THAT DETAILS AND NOTES ADDED |
| | TO PLANS ARE FROM THE 2001 FBC CHAPTER |
| | 13. |
| | PLEASE SEE THAT THE NOTES AND DESIGN DO |
| | NOT APPLY AS THE DESIGN SHALL BE UNDER |
| | THE 2004 FBC. PLEASE SEE THAT THE REST |
| | OF THE PLANS AND DESIGN ARE ALREADY |
| | UNDER THE 2004 FBC. |
| | MAY NOT USE 2001 FBC FOR CHAPTER 13 AND |
| | THE 2004 FOR ALL OTHER AREAS. |
| | |
| | 2) NOTE: PLEASE SEE ONLY COPY OF THE NEW |
| | ELECTRICAL E-1 WAS SUBMITTED AND THE |
| | E-2WHICH IS IN SETS WASFROM THE |
| | PREVIOUS SETS WHICH STILL CONTAINS THE |
| | OLD SEAL WHICH IS NOT ACCEPTABLE. PLEASE |
| | SEE NOTE #4. |
| | MIN OF TWO SETS ARE REQUIRED, SIGNED, |
| | DATED AND SEALED BY SAID ARCHITECTS; AND |
| | ENGINEER'S OF RECORD. |
| | PLEASE ALSO SEE THAT ALL PLANS SHALL BE |
| | CLEAR AND VISABLE WITH ALL INFORMATION. |
| | PLEASE KNOW THAT PLANS CONTAIN MANY |
| | HANDRAWN ITEMS WHICH ARE NOT EASILY READ |
| | AND PLANS NEED TO BE RE-DONE. |
| | PLEASE SEE FBC ADMIN SECT 106.1.3 |
| | 106.1.2,106.3.5 ETC |
| | |
| | 3) NOTE: " IMPORTANT" |
| | PLEASE SEE PREVIOUS REVIEW NOTES ALSO |
| | REQUESTED THAT WHEN PLANS ARE SUBMITTED, |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ANY OF THE SHEETS WHICH ARE STAMPED BY A |
| | TRADE AS "PASSED", THEN THOSE WILL STILL |
| | REMAIN IN NEW SETS. ONLY ONE SET OF ALL |
| | OLD/VOIDED REMOVED SHEETS SHALL BE |
| | SUBMITTED FOR REFERENCE. |
| | ** PLEASE KNOW, THIS WILL HELP TO |
| | EXPEDITE THE PLAN REVIEW PROCESS AS WE |
| | WILL NOT BE ABLE TO MAKE ALL SHEETS INTO |
| | COMPLETE SETS AND COULDDELAY THE |
| | PROJECT UNTIL THIS IS DONE. |
| | |
| | 4) NOTE: PLEASE SEE NOTE FROM 2ND REVIEW |
| | WHEN PLANS CAME BACK SEALED WITH A SEAL |
| | CONTAINING THE WORDING "CERTIFICATE" . |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001 WHICH CHANGED THE |
| | REQUIREMENT IN FEB 04 TO REQUIRE THE |
| | WORDING OF "LICENSE" IN SAID SEAL. |
| | PLEASE KNOW, AN EXTENSION WAS GRANTED BY |
| | THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEER'S TO THE DATE OF DEC 31, 2005. |
| | PLEASE SEE THE SHEET E-2 IS STILL THE |
| | OLD SHEET CONTAINING THE OLD SEAL. |
| | |
| | 5) NOTE: PLEASE PROVIDE UPDATED PLUMBING |
| | SHEETS AS THE SHEETS IN SETS WHICH WERE |
| | ALREADY STAMPED BY THE PLUMBING REVIEW |
| | NOW CONTAIN "WHITE-OUT" AND HANDRAWN |
| | CHANGES. PLEASE KNOW THESE SHEETS WHICH |
| | WERE ALREADY STAMPED HAVE NOW BEEN |
| | "VOIDED". PLEASE KNOW UNDER FS 481, 471 |
| | NO "WHITE-OUT" IS PERMITTED ON PLANS IN |
| | ANY MANNER. |
| | |
| | 6) NOTE: PLEASE KNOW BASED ON REPEAT |
| | COMMENTS FOR CODE COMPLIANCE THREE OR |
| | MORE TIMES FOR THE SAME CODE REQUIREMENT |
| | A FEE HAS BEEN ASSESSED AS REQUIRED |
| | UNDER FLORIDA STATUES 553.80(2)(B). |
| | PLEASE SEE THAT THE FS REQUIRES THIS FEE |
| | TO THE DESIGN PROFESSIONAL. |
| | PLEASE KNOW THE FEE MUST BE PAID BEFORE |
| | THE PLANS ARE RESUBMITTED FORNEXT |
| | REVIEW. |
| | THE AMOUNT OF $2203.20 IS NOW OWED. |
| | ** PLEASE KNOW ONE COPY OF EACH OF ALL |
| | OLD ELECTRICAL SHEETS ARE BEING RETAINED |
| | BY THE BUILDING OFFICAL FOR FILE AS THE |
| | BUILDING OFFICAL MAY SUBMIT FOR PEIR |
| | REVIEW BY THE FBPE'S AND BOARD'S LEGAL |
| | COUNSEL. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |