Text |
| 2006-03-06 00:00:00 | ******UNSAT ******** |
| | |
| | ** PLEASE SEE COMMENTS BELOW AND |
| | COMMENTS FROM OTHER TRADES DUE TO THE |
| | CHANGE IN OCCUPANCY AS NOTED FOR MEETING |
| | THE CURRENT CODES. |
| | |
| | |
| | 1)NOTE: PLEASE HAVE PLANS REFERENCE THE |
| | CURRENT CODES, 2003 NFPA-101, 2002 |
| | NFPA-72, AND 2002 NFPA-70. |
| | |
| | 3)NOTE: PLEASE SEE RISER INDICATES 3/0'S |
| | FOR 225A'S? PLEASE SEE 310.16, WHERE |
| | 3/0'S ARE ONLY RATED FOR 200A'S. |
| | |
| | 4)NOTE: PLEASE SHOW LOCATIONS OF ALL |
| | EXISITNG ELECTRICAL PANELS/EQUIPMENT. |
| | 215.5, 110.26,240.24,408.7 |
| | |
| | 5)NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1& .2, CONTROL OF |
| | LIGHTING. |
| | 13-413.1ABC.1, VOLTAGE DROP, PROVIDE |
| | INFORMATION. |
| | 13-415.1AB.1 |
| | PLEASE PROVIDE, SCHEDULING, CIRCUITING |
| | ETC. |
| | |
| | 6)NOTE: PLEASE SEE LOAD CALCUALTIONS |
| | WHICH SHOWS LOADS: 180A'S IS LESS THAN |
| | 208A'S?? PLEASE SEE 208A SERVICE COULD |
| | NOT BE LOCATED ON ANY PLANS/RISER. |
| | (MISPRINT).? |
| | |
| | 7)NOTE: PLEASE PROVIDE A MORE SPECIFIC |
| | DETAIL OF LOADS. |
| | 215.5/220 |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. ONE SET OF |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERNECE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |