| 2006-04-14 00:00:00 | 1) A DETAIL DRAWING OF THE NEW BATHROOM |
| | IS REQUIRED SHOWING ALL THE REQUIREMENTS |
| | FOR ACCESSIBILITY. SHOW THE DIMENTIONS |
| | FOR GRAB BARS, CLEAR FLOOR SPACE, TOILET |
| | PAPER HOLDER ETC. |
| | DOORS SHALL NOT SWING INTO THE FLOOR |
| | SPACE REQUIRED FOR ANY FIXTURE. |
| | SEC.11-4.23.2 |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) PLEASE STATE THE DIMENTIONS OF ALL |
| | OPENINGS/PASS-THROUGH ON DRAWINGS. |
| | |
| | 4) SUBMIT THE ELEVATION DRAWINGS FOR THE |
| | LOUNGE/RECEPTION OR |
| | ADMINISTRATION,REPAIR LAB AND ALL OTHER |
| | WORK AREAS SHOWING THE HEIGHT OF THE |
| | SINKS AND COUNTER TOPS ETC. OF THESE |
| | AREAS.SEE FBC SEC.11-7 |
| | |
| | 5) 11-4.13.6 MANEUVERING CLEARANCES AT |
| | DOORS . |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS |
| | THAT ARE NOT AUTOMATIC OR POWER-ASSISTED |
| | SHALL BE AS SHOWN IN FIGURE 11-25 . THE |
| | FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE LEVEL AND CLEAR. |
| | |
| | 6)IS THIS BUSINESS ON THE FIRST OR |
| | SECOND FLOOR. IF IT IS LOCATED ON THE |
| | SECOND FLOOR INDICATE THE ACCESSIBILITY |
| | TO THE AREA FOR THE HANDI-CAP. IF |
| | ELEVATORS ARE PROVIDED,STATE THE SIZE |
| | OF THE DOOR OPENINGS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |