Plan Review Notes
Plan Review Notes For Permit 06011238
Permit Number 06011238
Review Stop B
Sequence Number 5
Notes
Date Text
2007-07-02 17:02:09BUILDING REVIEW 5TH CHECKLIST:
  
 ***NOTE: PREVIOUS ENGINEER RESIGNED.THERE IS A NEW
 ENGINEER ON BOARD. NEW PLANS REVIEWED THIS TIME.
  
 1- SEE COMMENTS REGARDING FRONT PORCH.AREA
 TABULATIONS AND DRAWINGS TO BE REVISED ACCORDINGLY.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FLAT ROOF.NEED TO SPECIFY WHICH APPROVED
 ASSEMBLY AND FASTENING OPTION IS GOING TO BE USED AS
 REQUIRED BY CITY POLICY FOR ROOFING PERMITS. SEE
 ATTACHED COPY.
 *** ALSO, NEED TO PROVIDE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERALLIMITATION #7 ON LAST PAGE OF NOA
 03-0501.02 SUBMITTED.
  
 B) WINDOW MULLIONS.
  
 C) GLASS BLOCK.
  
 D) FRONT AND REAR SWING DOORS AS SHOWN ON PLANS.
  
 E) ARCHED WINDOWS AS SHOWN ON PLANS.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3. CITY AMENDMENTS TO FBC 2004.
 *** SOME OF THE PRODUCT APPROVALS SUBMITTED HAVE A
 REVIEWED & APPROVED STAMP.THIS INFORMATION ALONE IS
 NOT ADEQUATE BECASUE IS MISSINGTHE NAME OF THE
 ENGINEER APPROVING THE PRODUCT APPROVAL.
  
 4-A) INFORMATION ON NOTICE OF COMMENCEMENT IS
 INCOMPLETE.GENERAL DESCRIPTION OF IMPROVEMENT
 INFORMATION IS NOT PROVIDED.
  
 B) NEED RE-RECORDEDNOTICE OF COMMENCEMENT.IT WAS
 RECORDED ON 01/26/07. NOTICE OF COMMENCEMENT EXPIRES
 AFTER 90 DAYS IF WORK IS NOT STARTED. SEC. 713.13
 FLORIDA STATUTE.
  
 5- ENERGY CALCULATIONS:
 A) IF CALCULATIONS ARE NOT DONE FOR WORST CASE
 SCENARIO, THEN THEY MUST BE DONE REFLECTING THE ACTUAL
 HOUSE ORIENTATION.SEE SURVEY FOR CORRECT HOUSE
 ORIENTATION AND REVISE AS REQUIRED.
  
 B) OVERHANG HEIGHT IS INCORRRECT. REVISE AS
 REQUIRED.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 D) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 6- SHEET C1:
 A) SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC.
 602.1 FBC 2004.
  
 B) COMPONENTS AND CLADDING INFORMATIONIS VERY
 CONFUSING.SEE REVISED TABLE 1609.6.2.1(2) FBC 2004
 AND REVISE INFORMATION AS REQUIRED.
  
 7- SHEET A1:
 A) WHERE IS THE REAR COVERED PATIO SHOWED ON AREA
 CALCULATIONS?.ENTRY PORCH AREA NEED TO BE REVISED.
 SEE ZONING COMMENTS..
  
 B) FLOOR PLANS CALL FOR "PROVIDE V JOIST WHERE
 EXISTING MEETS PROPOSED? WHAT'S THIS FOR?. PROVIDE
 COMPLETE DETAIL. SEC. 106.1.2 CITY AMENDMETNS TOO FBC
 2004.
  
 8- SHEET A2:
 A) WINDOWS SHOWN AT NEW MASTER BATHROOM AND NEW
 FAMILY ROOM AREA DON'T MATCH TYPE OF WINDOW SPECIFIED
 ON PLANS. REVISE AS REQUIRED.
  
 9- SHEET A3:
 A) FLAT ROOF ASEMBLY SPECIFIED ON SEC. A/A-3 DOENS'T
 MATCH ASSEMBLY SHOWN ON SEC. B/A-3. REVISE AS
 REQUIRED.
  
 B) BUILDING SECTIONS TO SHOW HOW TO PROVIDE CROSS
 VENTILATION IN FLAT ROOF AS REQUIRED BY SEC. R806 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 C) SPECIFY FIREBLOCKING IN WALL SECTIONS AS REQUIRED
 BY SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 D) SEC. B/A-3:
 * SPECIFY HOW IS THE FOOTING COMPLYING WITH SEC.
 R403.1.4 OF 2004 FLORIDA RESIDENTIAL CODE.
 ** CLARIFY SPECS GIVEN TO BOND BEAM. INFORMATION TO
 MATCH OTHER BUILDING SECTIONS AND PLANS.
 *** ALL FRAMING MEMBERS SIZES TO MATCH ROOF FRAMING
 PLAN.
 **** CLARIFY HOW INSTALLING A 2X8 FASCIA ON A 2X12 ROOF
 JOIST?
  
 E) REVISE ROOF SHEATHING NAILING SPACING. SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE AND REVISE
 SPACING FOR ZONE 3AS REQUIRED.
  
 F) SEC. A/A-3:
 * CLARIFYINSTALLATION OF NEW ROOF JOIST TO EXISTING
 MASONRY WALL.PROVIDE ENLARGED DETAIL AND COMPLETE
 SPECS SHOWING HOW IS THE JOIST SECURED TO EXISTING BEAM
 USING SAIMPSON MTSM20 AND USING JOIST HANGER MUS26.
 NOTE: MUS26 IS A WOOD TO WOOD CONNECTOR. IT DOESN'T
 WORK FOR PROPOSED INSTALALTION.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
  
 10- PLEASE RETURNREVIEWED SET AFTER CORRECTIONS ARE
 DONE TO ORIGINAL PLANS TO EXPEDITE THE REVIEW PROCESS.
  
 11- PROVIDE STRUCTURAL BUCK DETAIL AND SPECS FOR DOORS.
 SEE PRODUCT APPROVAL FOR REQUIRED SIZE AND SEC.
 R613.6.2 OF 2004 FLORIDA RESIDETNAIL CODE FOR PROPER
 WAY OF INSTALLING BUCK.
  
 12- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N JOG RD (561)233-5115)SO THEY CAN
 UPDATE TOTAL SQUARE FOOTAGE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF ADDITINAL FEES ARE DUE.
  
 13- PROVIDESOIL TEST REPORT REFERENCED IN THE
 ARCHITECTURAL PLANS.
  
 14-PERMIT VALUATION WILL BE ADJUSTED AFTER FRONT
 PORCH ISSUE IS RESOLVED WITH ZONING.ADDITIONAL PERMIT
 VALUATION FEES FEES WILL BE CHARGED AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712