2007-06-19 15:18:26 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THERE IS A NOTE WITH THE CALCULATIONS THAT A "NEW
 200A SERVICE PROPOSED". SUBMIIT A RISER DIAGRAM PER
 215.5, AND PANEL SCHEDULE PER 408.4 (PLEASE SEE NEW
 VERBAGE),
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).
  
 3}PER R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS
 REQUIRED IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR. SEE ARTICLE FOR COMPLETE
 TEXT.LOCATE ON PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  