| Plan Review Notes For Permit 06011238 |
| Permit Number |
06011238 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-06-19 15:18:26 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} THERE IS A NOTE WITH THE CALCULATIONS THAT A "NEW | | | 200A SERVICE PROPOSED". SUBMIIT A RISER DIAGRAM PER | | | 215.5, AND PANEL SCHEDULE PER 408.4 (PLEASE SEE NEW | | | VERBAGE), | | | | | | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). | | | | | | 3}PER R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS | | | REQUIRED IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS | | | REQUIRING A PERMIT OCCUR. SEE ARTICLE FOR COMPLETE | | | TEXT.LOCATE ON PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|