Plan Review Notes
Plan Review Notes For Permit 06011238
Permit Number 06011238
Review Stop B
Sequence Number 4
Notes
Date Text
2007-03-01 17:30:09BUILDING REVIEW FOURTH CHECKLIST:
 1- ENGINEER NEEDS TO COORDINATE ALL DRAWINGS, DETAILS,
 CALCULATIONS AND SPECIFICATIONS. DRAWINGS ARE
 CONFUSING.
 *DETAILS DON'T MATCH.
 **THERE ARE DIFFERENT DESIGN PRESSURES SHOWN ON
 DRAWINGS 1 AND 6 AND ON SEPARATE DESIGN PRESSURES
 CALCULATIONS SUBMITTED.
 ***HURRICANE SHUTTERS NOTES DON'T MATCH INSTALLATION
 SCHEDULE INFORMATION.SHUTTERS INSTALLATION SPECS ARE
 NOT REQUIRED TO BE PART OF THE DRAWINGS. THIS
 INFORMATION IS PROVIDED IN THE SHUTTERS INSTALLATION
 SCHEDULE AND PRODUCT APPROVAL.
 ****SECTION 2/A1: HOW ISTHE 16" FOOTER 12" BELOW
 GRADE IF SECTION SHOWS 6" ABOVE GRADE?.
 *****FINISH FLOOR ELEVATIONS ARE CONSFUSING AND NOT
 MATCHING.FLOOR PLAN ON DRAWING #2 CALLS FOR STEP NO
 REQUIRED AT NEW MASTER BEDROOM, WHILE SHOWING A 7"
 STEP. ALSO, SEE FINISHED FLOR ELEVATION SHOWN ON PLANS
 AND ON SURVEY.
 ******SECTION 2/A7 CALLS FOR CONNECTOR HTSM20 TO
 SUPPORT 2X12 JOIST TO EXISTING WALL.PROVIDE COMPLETE
 DETAIL SHOWING INSTALLATION. THIS DETAIL DOESN'T WORK.
  
 *******HOW IS R30 INSULATION INSTALLED ON 2X12 JOIST
 TO ALLOW CROSS VENTILATION?.
 ********NOTES FOR FLAT ROOF NAIL ENHANCING MAKE NO
 SENSE.ROOF ZONES WERE INVERTED.ZONE 1 SPECIFIES
 MORE NAILS THAN ZONE 3 AND INFORMATION SHALL BE THE
 OTHER WAY AROUND. AND, NUMBER OF ROWS IS NOT CLEAR.
 *********ACCORDING TO THE EXTERIOR ELEVATIONS, THERE A
 SOME WINDOWS THAT NEED TO BE SPECIFIED WITH SAFETY
 GLASS AS REQUIRED BY SEC. R308.4 2004 FLORIDA
 RESIDENTAIL CODE. SEE MASTER BEDRO**OM WINDOW, FAMILY
 ROOM WINDOW, EXISTING BEDROOM WINDOW AND FAMILY ROOM
 WINDOW.
 ********SECTION 2/A1 DOESN'T MATCH FOUNDATION PLAN.
 ***********FLOOR PLAN CALLS FOR SINGLE HUNG WINDOW AT
 KITCHEN AREA, WHILE WINDOW SCHEDULE CALLS FOR FIXED
 WINDOW.NEED MATCHING INFORMATION.
  
 THESE ARE JUST A FEW ITEMS THAT NEED TO BE COORDINATED
 AND REVISED. ENGINEER TO REVIEW COMPLETE SET OF PLANS
 AND COORDINATE ACCORDINGLY.THIS IS THE FOURTH TIME
 PLANS ARE DENIED.ONE COPY OF PLANS WILL BE RETAINED
 IN THIS OFFICE TO BE SEND TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FORREVIEW.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER
 13 FBC 2004.
  
 3- NOTICE OF COMMENCEMENT HAS NO DESCRIPTION FOR
 GENERAL DESCRIPTION OF IMPROVEMENT. COMPLETE
 INFORMATION AND RE-RECORD THE NOTICE OF COMMENCEMENT.
  
 4- STORM SHUTTERS:
 *NO CLEAR WHAT TYPE OF ANCHOR WILL BE USED. SEE STORM
 SHUTTERS DRAWINGS AND CLEARLY IDENTIFY SPECIFIC
 ANCHOR.
 **OPENIG SIZE DOESN'T MATCH PLANS.
 ***DESIGN PRESSURES DON'T MATCH PLANS.
 ****SHUTTER SPAN IS WRONG. IT CAN'T BE THE SAME SIZE OF
 THE OPENING. ALSO, THEEDGE DISTANCENEED TO BE
 CONSIDERED. CLARIFY WHY USING 5" AS EDGE DISTANCE.
 *****ENGINEER TO REVIEW AND APPROVE IN WRITING STORM
 SHUTTERS PRODUCT APPROVAL, NOT SIGNING AND SEALING.
  
 5- ENGINEER TO REVIEW AND APPROVE IN WRITTING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. SOME OF
 THE PRODUCT APPROVALS SAY REVIEWED, BUT IT DOESN'T SAY
 WHO REVIEWED AND APPROVE IT. NEED TO BE CLEAR WHO
 REVIEWED AND APPROVED THEM.
  
 6- ENGINEER SEPARATE CALCULATIONS SUBMITTED:
 *ALL THESE CALCULATIONS ARE NOT REQUIRED. ONLY THING
 THAT WAS REQUIRED WAS THE RAS 117 CALCULATIONS FOR FLAT
 ROOF NAIL ENHANCING AT PERIMETER AND CORNER AREAS. REST
 OF CALCULATIONS ARE NOT REQUIRED. BESIDES, SOME
 CALCULATIONS DON'T MATCH INFORMATION SUBMITTED ON
 PLANS.
 **WHY USING 20SF AS TRIBUTARY AREA?
 ***FIRST PARAGRAPH ON PAGE 4 OF SUBMITTED CALCULATIONS
 STATES THAT GENERAL LIMITATION #7 ONLY APPLIES TO ZONE
 3. THIS IS WRONG. GENERAL LIMITATION #7 APPPLIES AT ALL
 TIMES WHEN THE DESIGN PRESSURES OF SELECTED FLAT ROOF
 SYSTEM IS LOWER THAN DESIGN PRESSURES REQUIRED TO BE
 RESISTED AT ALL ROOF AREAS. IN THIS CASE NEED TO
 PROVIDE NAIL ENHANCING FOR ZONE 2 AND ZONE 3. REVISE AS
 REQUIRED.
 ****ALSO, ON PAGE 4 OF SUBMITTED CALCULATIONS IS NOT
 CLEAR HOW MANY ROWS ARE REQUIRED.CLEARLY IDENTIFY
 SPACING AT THE LAP AND HOW MANY ADDITIONAL ROWS ARE
 REQUIRED. SEE PAGE 28 OF NOA 03-0501.02 SUBMITTED FOR
 PROPER WAY OF SPECIFYING FASTENER SPACING AND ROWS
 REQUIRED.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 *FIXED WINDOWS. SEE PLANS.
 **SINGLE HUNG WINDOWS.PRODUCT APPROVAL SUBMITTED WAS
 SUPERSEDED BY DADE COUNTY PRODUCT APPROVAL DIVISION.
 SEE ATTACHED COPY OF CURRENT NOA. ENGINEER TO REVIEW
 AND APPROVE THIS NEW NOA.
  
 8-ENGINEER TO PAY PLAN REVIEW FEES AS REQUIRED BY SEC.
 553.80(2)(B) FLORIDA STATUTE. SEE ATTACHED COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712