Date Text
2006-07-11 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} COMMENT #5 FROM THE PREVIOUS REVIEW:
 5} INDICATE IF THE SERVICE IS EXISTING
 AND THE RATING. PLEASE SUBMIT A RISER
 DIAGRAM PER 215.5., SHOW HOW THE
 RELOCATED PANEL IS BEING FED.
 THE RESUBMITTED PLAN INDICATES A 150 AMP
 EXISTING SERVICE. THE RISER ON THAT PLAN
 INDICATES A 200 AMP SERVICE. PLEASE
 CORRECT AND INDICATE WHAT IS PROPOSED
 UNDER THE SCOPE OF THIS APPLICATION.
  
 2} THE REFRIGERATOR ON THE SCHEDULE IS
 1500 VA, AND 1200 VA IN THE CALC. PLEASE
 CORRELATE.
  
 3} THE SMALL APPLIANCE CIRCUITS IN THE
 CALCS AND ON THE SCHEDULE DO NOT
 CORRELATE.
  
 4} THE JACUZZI LISTED ON THE SCHEDULE IS
 NOT IN THE CALCULATIONS.
  
 5} THE CIRCUIT NUMBERS ON THE PLAN AND
 THE ONES ON THE PANEL SCHEDULE DO NOT
 CORRESPOND.
  
 6} A SMOKE DETECTOR IS REQUIRED OUTSIDE
 THE BEDROOM AS WELL AS INSIDE PER 313.1
 FBC. THIS DEVICE WAS ON THE PREVIOUS
 PLAN , BUT REMOVED ON THIS ONE.
  
 7} KITCHEN RECEPTACLES MUST COMPLY WITH
 210.52(B).
  
 8} THE ENGINEER OF RECORD MUST SEAL THE
 DOCUMENTS WITH A SEALACCEPTABLETO
 THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  