Plan Review Notes
Plan Review Notes For Permit 06011238
Permit Number 06011238
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-19 00:00:00BUILDING REVIEW 2ND CHECKLIST:
  
 ***NOTE:
 A) ENGINEER'SPLANS ARE INCOMPLETE AND
 CONFUSING.
  
 B) ENGINEER TO SEE ATTACHED COPY OF FL.
 ST. 553.80(2)(B) REGARDING MULTIPLE
 REVIEWS OF DESIGN PROFESSIONALS
 DOCUMENTS.
  
 1- WALL LEGEND AND INFORMATION SHOWN ON
 FLOOR PLAN DON'T MATCH AND IS
 CONFUSING. UNABLE TO DETERMINE WHAT IS
 EXISTING AND WHAT'S NEW. THERE ARE MANY
 TYPES OF WALLS SHOWN IN FLOOR PLAN, BUT
 NOT IN THE WALL LEGEND.
  
 2- PLANS SHOW WALL LEADING TO THE NEW
 KITCHEN AREA TO BE REMOVED. ACCORDING TO
 PALM BEACH COUNTY PROPERTY APPRAISAL
 INFORMATION THIS IS A BEARING WALL.
 DRAWINGS DON'T SHOW ANY SPECIFICATIONS
 AND CONSIDERATION FOR REMOVAL OF BEARING
 WALL. NEED TO SHOW SHORING AND HOW IS
 EXISTING AND NEW STRUCTURE GOING TO BE
 SUPPORTED.
 ENGINEER TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 ADDRESSING THE STRUCTURAL
 STABILITY ISSUE. SECTION 106.1.2 OF CITY AMENDMENTS TO
 FBC 2004.
 ***PLANS SHOW LIKE THIS IS A NEW WALL.
 IS THIS A NEW WALL?
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT.
 ***NO DONE.
  
 4- AFTER ORIGINAL PLANS ARE REVISED BY
 THE ENGINEER, BRING THEM TO PALM BEACH
 COUNTY TO PAY IMPACT FEES. BRING BACK
 STAMPED DRAWINGS AND PAID RECEIPT.
 ***NO DONE.
  
 5- AS OF JANURARY 1ST 2006 ENGINEER
 NEEDS TO USE NEW SEAL AS REQUIRED
 BY FLORIDA ADMINISTRATIVE CODE.
 ***NO DONE. ENGINEER STILL USES THE SEAL
 READING "CERTIFICATE" NOT LICENSE.
  
 6- A) MASTER BEDROOM SPECIFIED AWNING
 WINDOW DOESN'T COMPLY WITH EGRESS
 REQUIREMENTS OF SECTION R310 2004
 RESIDENTIAL CODE. REVISE AS REQUIRED.
 B) FAMILY ROOM WINDOW (MAY ALSO BE AN
 SLEEPING ROOM) DOESN'T COMPLY WITH
 SECT.R310 2004 RESIDENTIAL CODE. REVISE
 AS REQUIRED.
 ***SINGLE HUNG WINDOWS SHOWN ON
 ELEVATIONS DON'T COMPLY WITH EGRESS.
 ALSO, CLEARLY SPECIFY SIZE OF WINDOW.
 SPECIFY WIDTH AND HEIGHT OF WINDOW.
  
 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR STORM SHUTTERS AS REQUIRED
 BY RULE 9B-72 OF DEPARTMENT OF COMMUNITY
 AFFAIRS.
 ***PROVIDE CLEAR AND LEGIBLE DRAWINGS.
  
 B) PROVIDE KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE FOR STORM
 SHUTTERS. SEE ATTACHED SAMPLE AND
 PROVIDE ALL THE REQUIRED INFORMATION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC.
 ***NO DONE.
  
 8- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL (REQ'D BY RULE 9B-72) FOR:
 A) FLAT ROOF SYSTEM (CLEARLY INDICATE
 WHICH OF THE APPROVED SYSTEMS IS GOING
 TO BE INSTALLED. CHECK IF LIMITATION #7
 OR #9 APPLIES AND PROVIDE REQUIRED
 INFORMATION).
 ***NO DONE. COMPLETE NOA SUBMITTED
 WITHOUT IDENTIFYING SPECIFIC APPROVED
 ASSEMBLY. AND, LIMITATION #7 CALLS FOR CALCULATIONS PER
 RAS 117. CALCULATIONS
 WERE NOT PROVIDED. BESIDES ENGINEER IS
 CONFUSING RAS CALCULATIONS FOR ROOF
 COVERING VS ROOF SHEATHING.
 ***NOTE: LIMITATION #9 CAN'T BE USED IN
 THIS AREA. DON'T COMPLY WITH DESIGN
 PRESSURES FOR CORNER & PERIMETER AREAS.
  
 ***DADE COUNTY NOA #01-0129.15 EXPIRED
 05/03/2006. NEED TO PROVIDE CURRENT NOA.
  
 B) ALL STRUCTURAL CONNECTORS.
 SPECIFIED ON PLANS. SEE PLANS & DETAILS.
 ***NO DONE.
  
 C) TYPE OF WINDOWS TO BE INSTALLED.
 ***ENGINEER CAN'T SIGN AND SEAL THIS
 PRODUCT APPROVAL. ONLY REVIEW & APPROVE
 IT. RE-SUBMIT NEW ONES
  
 D) EXTERIOR DOOR.
 ***ENGINEER CAN'T SIGN AND SEAL IT.
  
 E) CONCRETE LINTELS.
 ***NO DONE.
  
 9- ENGINEER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING (TYPICALLY DONE BY
 USING THE STANDARD REVIEW STAMP) ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO
 THIS OFFICE AS REQUIRED BY SEC. 106.3.3
 OF CITY AMENDMENTS TO FBC 2004.
 ***ENGINEER IS NOT ALLOWED TO SIGN AND
 SEAL THESE PRODUCT APPROVALS BECAUSE HE
 IS NOT THE DESIGNER. THE REQUEST WAS TO
 REVIEW AND APPROVE THEM, NOT SIGN AND
 SEAL THEM.
  
 10- ENGINEER TO SPECIFY CONCRETE
 LINTELS. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
 ***NO DONE.
  
 11- PROVIDE STRUCTURAL BUCK DETAIL FOR
 EXTERIOR DOOR. SEE SECTION R613.6.2 OF
 2004 RESIDENTIAL CODE FOR PROPER WAY OF
 INSTALLING STRUCTURAL BUCK. ALSO, CHECK
 PRODUCT APPROVAL FOR REQUIRED BUCK SIZE.
 ***NO DONE. IF USING STEEL DOOR WITH
 STEEL EDGE, THEN SPECIFY IT ON PLANS AND
 SPECIFY ATTACHMENT TO THE STRUCTURE. SEE
 PRODUCT APPROVAL.
  
 12- PROVIDE DETAIL/SECTION FOR STEEL
 COLUMN SHOWING CONNECTIONS AT TOP AND
 BOTTOM OR COLUMN. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 ***DETAIL IS WRONG. A) 1'-0" HIGH BRAKET
 FOR 2X8 BEAM?. B)SIZE OF COLUMN DOESN'T
 MATCH COLUMN SCHEDULE. C)FOUNDATION PLAN
 DOESN'T SHOW CONCRETE PAD. D) 8" SPACING
 FOR BOTTOM PLATE ANCHORS, WHILE BOTTOM
 PLATE IS ONLY 7" WIDE?. E)HOW MANY #3
 BARS IN FOOTING? F) TOP OF DETAIL
 DOESN'T MATCH ROOF FRAMING PLANS? G)IS
 THIS DETAIL FOR NEW COLUMN AT MASTER
 BEDROOM WING OR FOR NEW COLUMNS AT ENTRY
 PORCH?
  
 13- SPECIFY ROOF CROSS VENTILATION AS
 REQUIRED BY SEC. R806 2004 RESIDENTIAL
 CODE.
 ***HOW IS VENTILATION ACHIEVED IF
 SHOWING INSULATION ON THE EAVE AND THERE
 IS A (2)2X8 BEAM?
  
 14- DRAWING #1: A) REVISE CONCRETE COVER
 FOR FOUNDATION BEAM. SEE ACI 318-02.
 ***NO DONE. REVISE AS REQUIRED AND SEE
 ALSO STEEL NOTE AT BOTTOM OF STRUCTURAL
 NOTES ON SAME PAGE.
  
 ***FOUNDATION PLAN AND SITE PLAN DON'T
 MATCH. REVISE MASTER BEDROOM CLOSET
 CORNER AREA AS REQUIRED.
  
 B) SECTIONS AND DETAILS KEYED ON
 PLANS DON'T MATCH. COORDINATE ALL
 DETAILS AND SECTIONS AS REQUIRED.
 ***NO DONE. KEYED DETAILS ARE CONFUSING.
  
 C) PROVIDE ONLY THE DETAILS THAT
 APPLY TO THIS PROJECT. WHERE IS
 CONNECTOR SSTB16 GOING TO BE USED? AND
 HOW? SEC. 106.1.2 CITY AMENDMENTS FBC.
 ***NO DONE. THERE IS A LOT OF INFO. THAT
 DOESN'T APPLY TO THIS JOB.
  
 D) WHAT'S THE CONSTRUCTION OF
 EXTERIOR WALL AT MASTER BEDROOM CLOSET.
 THERE ARE NOT SPECS FOR COLUMNS, WALLS,
 BEAMS, ETC. PROVIDE COMPLETE
 INFORMATION. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 ***NO DONE. IT DOESN'T MATCH WALL LEGEND
  
 15- DRAWING #2: A) SPECIFY SAFETY GLASS
 FOR MASTER BATHROOM WINDOW. SEC. R308.4
 2004 RESIDENTIAL CODE.
 ***DESIGNER OF RECORD TO SPECIFY SAFETY
 GLASS. DON'T CITE CODE SECTION. PROVIDE
 SPECIFIC INFORMATION. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) WIND LOAD DESIGN PARAMETERS:
 CLARIFY IF BUILDING IS DESIGNED AS
 ENCLOSED OR PARTIALLY ENCLOSED. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***INTERNAL PRESSURE COEFFICIENT IS
 SPELLED GCPI, NOT CCPI. SEE ASCE -02.
  
 *** IF DESIGNED AS PARTIALLY OPEN, THEN
 WHY PROVIDING INFORMATION FOR STORM
 SHUTTERS? DO OTHER OPENINGS DON'T HAVE
 STORM SHUTTERS?. CLARIFY AS REQUIRED.
  
 C) HOW IS OPENING FOR DOOR TO BE
 REMOVED GOING TO BE ENCLOSED. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***IT'S NOT CLEAR WHAT'S NEW WALL. IF
 EXISTING WALL IS BEARING OR NOT.
  
 D) INFORMATION FOR STEEL COLUMN IN
 COLUMN SCHEDULE DOESN'T MATCH INFO. ON
 COLUMN SCHEDULE ON DRAWING #1.
  
 16- DRAWING #3: A) PROVIDE ONLY THE
 DETAILS THAT APPLY TO THIS PROJECT.
 ***ROOF COVERING INFORMATION IS NOT
 REQUIRED IN THIS DRAWING. ENGINEER IS
 CONFUSING ROOF COVERING WITH ROOF
 SHEATHING. PRODUCT APPROVAL LIMITATION
 #7 FOR FLAT ROOF SYSTEM REQUIRES
 CALCULATIONS DONE PER RAS 117. THIS IS
 DIFFERENT THAN CALCULATIONS DONE FOR
 ROOF SHEATHING. ENGINEER TO READ GENERAL LIMITATION #7
 ON LAST PAGE OF NOA AND
 PROVIDE THE REQUIRED CALCULATIONS.
  
 B) SHOW IN PLANS LOCATION OF BEAMS
 SPECIFIED ON THE BEAM SCHEDULE. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***WHICH ONE IS B1 AND WHICH IS B2?
  
 C) SHOW ROOF SLOPE AND ORIENTATION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC.
 ***NO DONE. FLAT ROOFS SLOPE IS NOT
 SPECIFIED ON ROOF PLAN.
  
 D) PROVIDE COMPLETE WALL SECTION AT
 MASTER BEDROOM CLOSET ROOF AREA TO SHOW:
 1) HOW IS (2)2X WOOD LEDGER SHOWN ON
 ROOF PLAN ATTACHED TO WALL. SPECIFY ALL
 SIZES AND FASTENERS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 ***DETAIL IS INCOMPLETE AND IT DOESN'T
 MATCH ROOF FRAMING PLAN AND ELEVATIONS.
  
 E) FLAT ROOF SYSTEM DETAIL: SEE
 FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 SELECTED FLAT ROOF SYSTEM. SEE IF
 SELECTED SYSTEM IS LIMITED BY GENERAL
 LIMITATION #7 OR #9. THEN, PROVIDE
 REQUIRED INFORMATION. DETAIL IS NOT
 REQUIRED. ONLY INFORMATION REQUIRED ON
 THE PRODUCT APPROVAL ITSELF.
 ***ENGINEER IS CONFUSING ROOF SHEATHING
 WITH RAS 117 CALCULATIONS FOR ROOF
 COVERING AT CORNER AND PERIMETER AREAS.
 SEE GENERAL LIMITATION #7 ON LAST PAGE
 OF THE NOA AND SUBMIT THE CALCULATIONS.
  
 F) WHERE IS THE STEEL COLUMN DETAIL
 TAKEN AT?. INFORMATION DOESN'T MATCH
 ROOF FRAMING PLAN.
  
 17- DRAWING #6: A) PROVIDE DETAIL/
 SECTION SHOWING HOW ARE NEW COLUMNS
 ATTACHED TO EXISTING ENTRY ROOF. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***NO DONE.
  
 B) WINDOW SECTION 5/A6: SEE SECTION
 R613.6.2 2004 RESIDENTIAL CODE FOR
 PROPER BUCK ATTACHMENT AND REVISE
 DETAIL AS REQUIRED.
 ***DETAIL WAS DELETED. PROVIDE DETAIL
 AND SEE COMMENTS ABOVE.
  
 C) WINDOWS ARE NOT DRAWN CORRECTLY.
 SHOW SINGLE HUNG WINDOWS AS SPECIFIED ON
 PLANS.
  
 18- DRAWING #7:
 A) WALL SECTION AA: 1) SHOW HOW IS
 CROSS VENTILATION ACHIEVED. SEC.R806
 2004 RESIDENTIAL CODE.
 ***SHOWING INSULATION ON THE EAVE? THIS
 IS BLOCKING THE VENTILATION. ALSO, THERE
 IS A (2)2X8 BEAM BLOCKING THE
 VENTILATION.
  
 B) CONCRETE TIE BEAM SHOWS ONLY 2 #5
 BARS. REVISE AS REQUIRED.
 ***TIE BEAM SIZE DOESN'T MATCH SCHEDULE.
  
 C) SPECIFY FASTENING TYPE AND SPACING
 OF 3/4 PLYWOOD ROOF SHEATHING. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***ENGINEER IS MIXING AND MATCHING ROOF
 SHEATHING WITH RAS 117 CALCULATIONS FOR
 FLAT ROOF BASE SHEET. REVISE AS REQ'D.
  
 D) WHERE IS SECTION AA TAKEN AT?.
 SHOW IT IN FLOOR/FOUNDATION PLAN TO
 VERIFY CONSISTENCY WITH PROPOSED
 CONSTRUCTION.
 ***KEYED WRONG ON FLOOR PLANS.
  
 E) PROVIDE ONLY THE DETAILS AND NOTES
 THAT APPLY TO THIS JOB.
  
 F) WALL SECTION AA: CLARIFY WHY IS
 THERE A NOTE SPECIFYING "MONOLITHIC
 CONCRETE SLAB AND FOOTING" IF THE
 DRAWING IS SHOWING A STEM WALL AND
 CONCRETE SLAB IS SEPARATED FROM THE
 FOOTING?.
  
 G) WALL SECTION 2/A8 DOESN'T MATCH
 ROOF FRAMING PLAN. REVISE AS REQUIRED.
  
 H) **INTERIOR WALL FRAMING DETAILS
 CALL FOR 2X4 WALLS. FLOOR PLAN CALLS FOR
 6" PARTITIONS. REVISE/CLARIFY AS
 REQUIRED.
 **SHOW IN FLOOR PLAN WALLS THAT
 WILL HAVE THE R-19 INSULATION SHOWN ON
 DETAILS. **NOTE: R-19 DOESN'T WORK ON
 2X4 WALL. SEE MANUFACTURER SPECS.
  
 19- PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 20- PROVIDE ENERGY CALCULATIONS AS
 REQUIRED BY CHAPTER 13 FBC 2004.
  
 21- SURVEY SUBMITTED SHOWS EXISTING
 PORCH WHERE PROPOSED FAMILY ROOM AND
 KITCHEN AREA ARE GOING TO BE. ENGINEER
 DRAWING #1 CALLS FOR NEW CONCRETE SLAB
 ON COMPACTED FILL. CLARIFY IF REMOVING
 EXISTING CONCRETE SLAB AND PROVIDING NEW
 COMPACTED FILL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 22- ALL DRAWINGS TO BE CLEAR AND
 LEGIBLE. SOME INFORMATION IS TO LIGHT
 AND BLURRY AND HARD TO READ. REVISE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712