Plan Review Notes
Plan Review Notes For Permit 06011238
Permit Number 06011238
Review Stop P
Sequence Number 1
Notes
Date Text
2006-02-10 00:00:00DENIED;
 1. IF BUILDING DRAIN IS OUT SIDE THE
 UNIT CLEANOUTS WILL BE REQUIRED ON
 TOILET DRAIN AND TUB DRAIN. SEE ONE SET
 OF DRAWINGS MARKED IN RED.
 2. PLEASE REMOVE, PLUMBING NOTES 2,3,
 AND 4. NOTE 5.COPPER UNDER SLAB WILL BE
 "L" COPPER, GALV. WATER PIPING CAN NOT
 BE INSTALLED UNDER GROUND BECAUSE OF
 CORROSION.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
 TWO SETS OF PLANS ARE REQUIRED.