| Plan Review Notes For Permit 06011238 |
| Permit Number |
06011238 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-10 00:00:00 | DENIED; | | | 1. IF BUILDING DRAIN IS OUT SIDE THE | | | UNIT CLEANOUTS WILL BE REQUIRED ON | | | TOILET DRAIN AND TUB DRAIN. SEE ONE SET | | | OF DRAWINGS MARKED IN RED. | | | 2. PLEASE REMOVE, PLUMBING NOTES 2,3, | | | AND 4. NOTE 5.COPPER UNDER SLAB WILL BE | | | "L" COPPER, GALV. WATER PIPING CAN NOT | | | BE INSTALLED UNDER GROUND BECAUSE OF | | | CORROSION. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | TWO SETS OF PLANS ARE REQUIRED. |
|