| 2006-02-10 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE LOAD CALCULATIONS AND THE PANEL |
| | SCHEDULE DO NOT MATCH. SEE OVEN, DRYER, |
| | REFRIGERATOR, A/C. |
| | |
| | 2} THE OVEN LOAD FOR CALCULATION MUST BE |
| | A MINIMUM OF 8KW PER 220.19 |
| | |
| | 3} THE DRYER MINIMUM LOAD IS 5KW PER |
| | 220.18. |
| | |
| | 4} THE BATH CIRCUIT ON THE PANEL |
| | SCHEDULE INDICATES A 15 AMP CIRCUIT. |
| | 20AMPS IS REQUIRED PER 210.11(C)(3). |
| | |
| | 5} INDICATE IF THE SERVICE IS EXISTING |
| | AND THE RATING. PLEASE SUBMIT A RISER |
| | DIAGRAM PER 215.5., SHOW HOW THE |
| | RELOCATED PANEL IS BEING FED. |
| | |
| | 6} 210.52(C)(3)- PENINSULAR COUNTER |
| | SPACES. AT LEAST ONE RECEPTACLE OUTLET |
| | SHALL BE INSTALLED AT EACH PENINSULAR |
| | COUNTER SPACE WITH A LONG DIMENSION OF |
| | 600 MM (24 IN.) OR GREATER AND A SHORT |
| | DIMENSION OF 300 MM (12 IN.) OR GREATER. |
| | A PENINSULAR COUNTERTOP IS MEASURED FROM |
| | THE CONNECTING EDGE. |
| | |
| | 7} A SMOKE DETECTOR IS REQUIRED IN THE |
| | MASTER BEDROOM PER 313.1 FBC. |
| | |
| | PLEASE NOTE THAT TWO SETS OF PLANS ARE |
| | REQUIRED TO BE SUBMITTED FOR REVIEW PER |
| | 106.1 FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASER CALL. |
| | |
| | |