Plan Review Notes
Plan Review Notes For Permit 06011238
Permit Number 06011238
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-10 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATIONS AND THE PANEL
 SCHEDULE DO NOT MATCH. SEE OVEN, DRYER,
 REFRIGERATOR, A/C.
  
 2} THE OVEN LOAD FOR CALCULATION MUST BE
 A MINIMUM OF 8KW PER 220.19
  
 3} THE DRYER MINIMUM LOAD IS 5KW PER
 220.18.
  
 4} THE BATH CIRCUIT ON THE PANEL
 SCHEDULE INDICATES A 15 AMP CIRCUIT.
 20AMPS IS REQUIRED PER 210.11(C)(3).
  
 5} INDICATE IF THE SERVICE IS EXISTING
 AND THE RATING. PLEASE SUBMIT A RISER
 DIAGRAM PER 215.5., SHOW HOW THE
 RELOCATED PANEL IS BEING FED.
  
 6} 210.52(C)(3)- PENINSULAR COUNTER
 SPACES. AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH PENINSULAR
 COUNTER SPACE WITH A LONG DIMENSION OF
 600 MM (24 IN.) OR GREATER AND A SHORT
 DIMENSION OF 300 MM (12 IN.) OR GREATER.
 A PENINSULAR COUNTERTOP IS MEASURED FROM
 THE CONNECTING EDGE.
  
 7} A SMOKE DETECTOR IS REQUIRED IN THE
 MASTER BEDROOM PER 313.1 FBC.
  
 PLEASE NOTE THAT TWO SETS OF PLANS ARE
 REQUIRED TO BE SUBMITTED FOR REVIEW PER
 106.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASER CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW