2006-03-18 00:00:00BUILDING REVIEW CHECKLIST:
 1- PLANS SHOW WALL LEADING TO THE NEW
 KITCHEN AREA TO BE REMOVED. ACCORDING TO
 PALM BEACH COUNTY PROPERTY APPRAISAL
 INFORMATION THIS IS A BEARING WALL.
 DRAWINGS DON'T SHOW ANY SPECIFICATIONS
 AND CONSIDERATION FOR REMOVAL OF BEARING
 WALL. NEED TO SHOW SHORING AND HOW IS
 EXISTING AND NEW STRUCTURE GOING TO BE
 SUPPORTED.
 ENGINEER TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS ADDRESSING THE STRUCTURAL
 STABILITY ISSUE. SECTION 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- PROVIDE 2 COPIES OF PLANS, PRODUCT
 APPROVALS AND OTHER SUBMITTALS.
  
 4- AFTER ORIGINAL PLANS ARE REVISED BY
 THE ENGINEER, BRING THEM TO PALM BEACH
 COUNTY TO PAY IMPACT FEES. BRING BACK
 STAMPED DRAWINGS AND PAID RECEIPT.
  
 5- AS OF JANURARY 1ST 2006 ENGINEER
 NEEDS TO USE NEW SEAL AS REQUIRED
 BY FLORIDA ADMINISTRATIVE CODE.
  
 6- A) MASTER BEDROOM SPECIFIED AWNING
 WINDOW DOESN'T COMPLY WITH EGRESS
 REQUIREMENTS OF SECTION R310 2004
 RESIDENTIAL CODE. REVISE AS REQUIRED.
 B) FAMILY ROOM WINDOW (MAY ALSO BE AN
 SLEEPING ROOM) DOESN'T COMPLY WITH
 SECT.R310 2004 RESIDENTIAL CODE. REVISE
 AS REQUIRED.
  
 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR STORM SHUTTERS AS REQUIRED
 BY RULE 9B-72 OF DEPARTMENT OF COMMUNITY
 AFFAIRS.
 B) PROVIDE KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE FOR STORM
 SHUTTERS. SEE ATTACHED SAMPLE AND
 PROVIDE ALL THE REQUIRED INFORMATION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 8- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL (REQ'D BY RULE 9B-72) FOR:
 A) FLAT ROOF SYSTEM (CLEARLY INDICATE
 WHICH OF THE APPROVED SYSTEMS IS GOING
 TO BE INSTALLED. CHECK IF LIMITATION #7
 OR #9 APPLIES AND PROVIDE REQUIRED
 INFORMATION).
 B) ALL STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS. SEE PLANS & DETAILS.
 C) TYPE OF WINDOWS TO BE INSTALLED.
 D) EXTERIOR DOOR.
 E) CONCRETE LINTELS.
 F) WINDOW MULLIONS. SEE PLANS
  
 9- ENGINEER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING (TYPICALLY DONE BY
 USING THE STANDARD REVIEW STAMP) ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO
 THIS OFFICE AS REQUIRED BY SEC. 106.3.3
 OF CITY AMENDMENTS TO FBC 2004.
  
 10- ENGINEER TO SPECIFY CONCRETE
 LINTELS. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004
  
 11- ENGINEER TO SPECIFY ON PLANS WHICH
 OPENINGS ARE LOCATED IN ZONE 4 AND ZONE
 5 TO VERIFY COMPLIANCE WITH PRODUCT
 APPROVALS SUBMITTED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 12- PROVIDE STRUCTURAL BUCK DETAIL FOR
 EXTERIOR DOOR. SEE SECTION R613.6.2 OF
 2004 RESIDENTIAL CODE FOR PROPER WAY OF
 INSTALLING STRUCTURAL BUCK. ALSO, CHECK
 PRODUCT APPROVAL FOR REQUIRED BUCK SIZE.
  
 13- PROVIDE DETAIL/SECTION FOR STEEL
 COLUMN SHOWING CONNECTIONS AT TOP AND
 BOTTOM OR COLUMN. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 14- SPECIFY ROOF CROSS VENTILATION AS
 REQUIRED BY SEC. R806 2004 RESIDENTIAL
 CODE.
  
 15- DRAWING #1: A) COLUMN C3 CALLS FOR 4
 # 5 VERTICAL BARS. FOUNDATION PLAN SHOWS
 ONLY 2. REVISE AS REQUIRED.
 B) REVISE SPACING FOR CONCRETE BLOCK
 VERTICAL REINFORCEMENT. SEE REINF. CELL
 SPLICEDETAIL ON DRAWING #7.
 C) SIZE OF FOOTING IN FOUNDATION
 SCHEDULE NOTES AND FOOTING SIZE ON WALL
 SECTION DON'T MATCH. REVISE AS REQUIRED.
 D) REVISE CONCRETE COVER FOR FOUNDATION
 BEAM. SEE ACI 318-02.
 E) SECTIONS AND DETAILS KEYED ON
 PLANS DON'T MATCH. COORDINATE ALL
 DETAILS AND SECTIONS AS REQUIRED.
 F) UPDATE REFERENCE FOR CONCRETE SLAB
 WIRE MESH SUPPORTS. SEE 2004 RESIDENTIAL
 CODE FOR PROPER REFERENCE.
 G) STRUCTURAL NOTES: SPECIFY CURRENT
 FLORIDA BUILDING CODE EDITION FOR WHICH
 STRUCTURE IS DESIGNED (2004).
 H) PROVIDE ONLY THE DETAILS THAT
 APPLY TO THIS PROJECT. WHERE IS
 CONNECTOR SSTB16 GOING TO BE USED? AND
 HOW? SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004
 I) WHAT'S THE CONSTRUCTION OF
 EXTERIOR WALL AT MASTER BEDROOM CLOSET.
 THERE ARE NOT SPECS FOR COLUMNS, WALLS,
 BEAMS, ETC. PROVIDE COMPLETE
 INFORMATION. SEC. 106.1.2 CITY
 AMENDMETNS TO FBC 2004
  
 16- DRAWING #2: A) SPECIFY SAFETY GLASS
 FOR MASTER BATHROOM WINDOW. SEC. R308.4
 2004 RESIDENTIAL CODE.
 B) WIND LOAD DESIGN PARAMETERS:
 CLARIFY IF BUILDING IS DESIGNED AS
 ENCLOSED OR PARTIALLY ENCLOSED. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 C) HOW IS OPENING FOR DOOR TO BE
 REMOVED GOING TO BE ENCLOSED. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 17- DRAWING #3: A) PROVIDE ONLY THE
 DETAILS THAT APPLY TO THIS PROJECT.
 B) SHOW IN PLANS LOCATION OF BEAMS
 SPECIFIED ON THE BEAM SCHEDULE. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 C) SHOW ROOF SLOPE AND ORIENTATION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 D) PROVIDE COMPLETE WALL SECTION AT
 MASTER BEDROOM CLOSET ROOF AREA TO SHOW:
 1) HOW IS (2)2X WOOD LEDGER SHOWN ON
 ROOF PLAN ATTACHED TO WALL. SPECIFY ALL
 SIZES AND FASTENERS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 2) CONNECTOR SPECIFIED ON DETAIL 2/A3
 IS A TENSION TIE. SHOW INSTALLATION AND
 HOW IS ROOF CONNECTION DESIGNED FOR
 UPLIFT LOADS. SEE CATALOGUE FOR PROPER
 CONNECTOR INSTALLATION AND USE.
 E) ROOF FRAMING PLAN SHOWS (2)2X WOOD
 MEMBERS AT THE WEST SIDE OF ROOF BY NEW
 KITCHEN AREA: 1) HOW IS CROSS
 VENTILATION ACHIEVED?
 2) SPECIFY SPACING OF MTSM20
 CONNECTOR.
 F) FLAT ROOF SYSTEM DETAIL: SEE
 FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 SELECTED FLAT ROOF SYSTEM. SEE IF
 SELECTED SYSTEM IS LIMITED BY GENERAL
 LIMITATION #7 OR #9. THEN, PROVIDE
 REQUIRED INFORMATION. DETAIL IS NOT
 REQUIRED. ONLY INFRMATION REQUIRED ON
 THE PRODUCT APPROVAL ITSELF.
  
 18- DRAWING #6: A) MISSING SOUTH
 ELEVATION.
 B) EAST ELEVATION IS MISSING THE FLAT
 ROOF SYSTEM ABOVE MASTER BEDROOM CLOSET
 AREA. REVISE AS REQUIRED.
 C) PROVIDE COMPLETE SPECS FOR
 FASTENERS AND SPACING FOR ENTRY ROOF
 DETAIL. SEC. 106.1.2 CITY AMENDMENTS.
 D) PROVIDE DETAIL/SECTION SHOWING HOW
 ARE NEW COLUMNS ATTACHED TO EXISTING
 ENTRY ROOF. SEC. 106.1.2 CITY AMENDMENTS
 E) WINDOW SECTION 5/A6: SEE SECTION
 R613.6.2 2004 RESIDENTIAL CODE FOR
 PROPER BUCK ATTACHMENT AND REVISED
 DETAIL AS REQUIRED.
  
 19- DRAWING #7:
 A) WALL SECTION AA: 1) SHOW HOW IS
 CROSS VENTILATION ACHIEVED. SEC.R806
 2004 RESIDENTIAL CODE.
 B) CONCRETE TIE BEAM SHOWS ONLY 2 #5
 BARS. REVISE AS REQUIRED.
 C) SPECIFY FASTENING TYPE AND SPACING
 OF 3/4 PLYWOOD ROOF SHEATHING. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 D) WHERE IS THIS SECTION TAKEN AT?.
 SHOW IT IN FLOOR/FOUNDATION PLAN TO
 VERIFY CONSISTENCY WITH PROPOSED
 CONSTRUCTION.
 E) REVISE SIZE SPECS FOR DOWEL AT
 EXISTING FOUNDATION. SEE DWG FOR
 COMMENTS.
 F) WWM NOTE SAYS TO DOUBLE WWM AT
 STRESS POINTS. SHOW STRESS POINTS IN
 FOUNDATION PLAN. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 G) CONNECTOR LTT20B IS SHOWN AT THE
 BOTTOM OF JOIST. DETAIL SHOWS
 INSTALLATION AT TOP OF JOIST. THIS IS A
 TENSION TIE CONNECTOR. PROVIDE COMPLETE
 ENGINEERING SHOWING WHY USING CONNECTOR
 AT BOTTOM. SEC. 106.1.2 CITY AMENDMENTS
 FBC 2004.
 H) GENERAL NOTES AND CONCRETE NOTES
 ARE NOT LEGIBLE. REVISE AS REQUIRED.
 I) PROVIDE ONLY THE DETAILS AND NOTES
 THAT APPLY TO THIS JOB.
  
 20- PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 JULIO GOMEZ