Plan Review Notes
Plan Review Notes For Permit 06011232
Permit Number 06011232
Review Stop B
Sequence Number 5
Notes
Date Text
2007-06-13 17:24:38 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*. SCOPE OF WORK FROM ORIGINAL PERMIT HAS
 INCREASED PLEASE ADJUST PERMIT VALUE ACCORDINGLY
  
 2)IN AN EXISTING BUILDING A DESIGN PROFESSIONAL MUST
 ELECT THE LEVEL OF ALTERATION PER 301.5 OF EXISTING
 BUILDING CODE AND STATE ALONG WITH THE TYPE OF
 CONSTRUCTION ON THE DRAWINGS. ORIGINAL PERMIT SET WAS A
 LEVEL ONE ALTERATION AT THIS STAGE THE SCOPE OF WORK
 SHALL BE AT MIN A LEVEL TWO AND IF OVER 50% A LEVEL
 THREE.
  
 3)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 4) AS ON ORIGINAL PERMIT SET PROVIDE WIND DESIGN DATA
 ON DRAWINGS PER
 1603.1.4 FBC THIS INFORMATION IS REQUIRED TO COVER THE
 STRUCTURAL WORK PERFORMED ON EXTERIOR WALLS PER S/1
 THROUGH S/5 OF STRUCTURAL DRAWINGS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  