| Plan Review Notes For Permit 06011232 |
| Permit Number |
06011232 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-06-13 17:24:38 | | | | | | | DENIED | | | | | | 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC*. SCOPE OF WORK FROM ORIGINAL PERMIT HAS | | | INCREASED PLEASE ADJUST PERMIT VALUE ACCORDINGLY | | | | | | 2)IN AN EXISTING BUILDING A DESIGN PROFESSIONAL MUST | | | ELECT THE LEVEL OF ALTERATION PER 301.5 OF EXISTING | | | BUILDING CODE AND STATE ALONG WITH THE TYPE OF | | | CONSTRUCTION ON THE DRAWINGS. ORIGINAL PERMIT SET WAS A | | | LEVEL ONE ALTERATION AT THIS STAGE THE SCOPE OF WORK | | | SHALL BE AT MIN A LEVEL TWO AND IF OVER 50% A LEVEL | | | THREE. | | | | | | 3)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 | | | FBC. BE SURE THAT THEY ARE SIGNED AND | | | DATED BY PREPARER AND OWNER/AGENT PRIOR | | | TO SUBMITTAL | | | | | | 4) AS ON ORIGINAL PERMIT SET PROVIDE WIND DESIGN DATA | | | ON DRAWINGS PER | | | 1603.1.4 FBC THIS INFORMATION IS REQUIRED TO COVER THE | | | STRUCTURAL WORK PERFORMED ON EXTERIOR WALLS PER S/1 | | | THROUGH S/5 OF STRUCTURAL DRAWINGS | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | |
|