Plan Review Notes
Plan Review Notes For Permit 06011232
Permit Number 06011232
Review Stop E
Sequence Number 4
Notes
Date Text
2007-07-25 15:44:57 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). NONE ARE IN THE PANEL
 SCHEDULES.SAME AS PREVIOUS REVIEW COMMENT.
  
 2} } PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP
 AND CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE FOR 2005
 NEC: "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT
 DETAIL TO ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM
 ALL OTHERS." GENERAL LIGHTING" DOES NOT MEET THE
 INTENT.
  
 3} PER 240.24(D),.OVERCURRENT DEVICES SHALL NOT BE
 LOCATED IN THE VICINITY OF EASILY IGNITIBLE MATERIAL,
 SUCH AS IN CLOTHES CLOSETS. THE AHU DISCONNECT LOCATED
 IN THE CLOSET ON THE FIRST FLOOR, OR THE UNIT ITSELF
 HAVING OCP INSTALLED INTERNALLY, WOULD BE A
 VIOLATION.THIS COMMENT WAS ALSO IN THE PREVIOUS
 REVIEW.
  
 4} PANEL "A" DOES NOT MEET THE 3' CLEARANCE REQUIREMENT
 OF 110.26. SAME COMMENT AS PREVIOUS REVIEW.
  
 5}A RECEPTACLE IS REQUIRED ON THE 1' COUNTERTOP NEXT
 TO THE RANGE, FIRST FLOOR. 210.52(C)(1). SAME AS
 PREVIOUS REVIEW.
  
 SEE FS 553.80()(B), ATTACHED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676