| 2007-07-25 15:44:57 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW |
| | |
| | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). NONE ARE IN THE PANEL |
| | SCHEDULES.SAME AS PREVIOUS REVIEW COMMENT. |
| | |
| | 2} } PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP |
| | AND CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE FOR 2005 |
| | NEC: "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT |
| | DETAIL TO ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM |
| | ALL OTHERS." GENERAL LIGHTING" DOES NOT MEET THE |
| | INTENT. |
| | |
| | 3} PER 240.24(D),.OVERCURRENT DEVICES SHALL NOT BE |
| | LOCATED IN THE VICINITY OF EASILY IGNITIBLE MATERIAL, |
| | SUCH AS IN CLOTHES CLOSETS. THE AHU DISCONNECT LOCATED |
| | IN THE CLOSET ON THE FIRST FLOOR, OR THE UNIT ITSELF |
| | HAVING OCP INSTALLED INTERNALLY, WOULD BE A |
| | VIOLATION.THIS COMMENT WAS ALSO IN THE PREVIOUS |
| | REVIEW. |
| | |
| | 4} PANEL "A" DOES NOT MEET THE 3' CLEARANCE REQUIREMENT |
| | OF 110.26. SAME COMMENT AS PREVIOUS REVIEW. |
| | |
| | 5}A RECEPTACLE IS REQUIRED ON THE 1' COUNTERTOP NEXT |
| | TO THE RANGE, FIRST FLOOR. 210.52(C)(1). SAME AS |
| | PREVIOUS REVIEW. |
| | |
| | SEE FS 553.80()(B), ATTACHED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |