2007-06-18 15:36:29 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). NONE ARE IN THE PANEL
 SCHEDULES.
  
 2}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} PER 240.24(D),.OVERCURRENT DEVICES SHALL NOT BE
 LOCATED IN THE VICINITY OF EASILY IGNITIBLE MATERIAL,
 SUCH AS IN CLOTHES CLOSETS. THE AHU DISCONNECT LOCATED
 IN THE CLOSET ON THE FIRST FLOOR, OR THE UNIT ITSELF
 HAVING OCP INSTALLED INTERNALLY, WOULD BE A VIOLATION.
  
 4} PANEL "A" DOES NOT MEET THE 3' CLEARANCE REQUIREMENT
 OF 110.26.
  
 5}A RECEPTACLE IS REQUIRED ON THE 1' COUNTERTOP NEXT
 TO THE RANGE, FIRST FLOOR. 210.52(C)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER