| Plan Review Notes For Permit 06011232 |
| Permit Number |
06011232 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-06-18 15:36:29 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). NONE ARE IN THE PANEL | | | SCHEDULES. | | | | | | 2}PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 3} PER 240.24(D),.OVERCURRENT DEVICES SHALL NOT BE | | | LOCATED IN THE VICINITY OF EASILY IGNITIBLE MATERIAL, | | | SUCH AS IN CLOTHES CLOSETS. THE AHU DISCONNECT LOCATED | | | IN THE CLOSET ON THE FIRST FLOOR, OR THE UNIT ITSELF | | | HAVING OCP INSTALLED INTERNALLY, WOULD BE A VIOLATION. | | | | | | 4} PANEL "A" DOES NOT MEET THE 3' CLEARANCE REQUIREMENT | | | OF 110.26. | | | | | | 5}A RECEPTACLE IS REQUIRED ON THE 1' COUNTERTOP NEXT | | | TO THE RANGE, FIRST FLOOR. 210.52(C)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6676 | | 2007-06-06 08:24:48 | | | | | | | |
|