| Plan Review Notes For Permit 06011232 |
| Permit Number |
06011232 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-14 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT A RISER DIAGRAM | | | INDICATING THE SERVICE RATING, ALSO SHOW | | | GOUNDING PER 250.66 AND250.52. | | | | | | 2} THE LOAD CALCULATION MUST BE DONE PER | | | 220 PART II OR 220.31(B)OPTIONAL WITH | | | EXISTING A/C. | | | | | | 3} PLEASE SEE 210.52(E) AND 210.63 FOR | | | OUTSIDE RECEPTACLE REQUIREMENTS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|